Automatic excess pressure cut-off safety function
In TEST and PUMP mode the pump switches off if a pressure of 170 mbar is exceeded.
In PUMP mode, if the pressure falls below 160 mbar again, the pump switches on
automatically.
Stand-by mode
In stand-by mode (status when the electronic test device is switched on or when the PUMP or
TEST functions are deselected) the last measured or current pressure is displayed in mbar.

LED AND DISPLAY

LEDs in operating status
The operating status of the electronic test device is shown by four LEDs.
LCD display in operating status
The display shows different information depending on the operating status of the electronic
test device. If "LO BAT" (low battery) is shown in the display, charge the battery with the
enclosed wall plug transformer.
In stand-by mode, the installed no-maintenance battery is switched off automatically if no
buttons are pressed for approx. 30 seconds (deep discharge protection). The On button is
used to switch the electronic test device on again.
Use only the enclosed wall plug transformer to charge the battery and to operate the
electronic test device and the connected printer.

START-UP

Do not connect the test hose from the electronic test device to the supply line before the leak
check.
part no. 27 105 51
Elektronic test device Leak Check LPG PRO
lit: continuously when the electronic test
device is switched on.
lit: leak check phase 1:
Pressure build-up
flashing: leak check phase 2:
Resting time
flashing: leak check phase 3:
Measuring time
lit: leak check phase 4:
Results display (pressure difference in
mbar)
lit: Error, error code displayed
7 / 12