Thermozone AD 200 A/E/W
Output charts water
Type
Fan
position
AD210W
max
min
AD215W
max
min
AD220W
max
min
Type
Fan
position
AD210W
max
min
AD215W
max
min
AD220W
max
min
Type
Fan
position
AD210W
max
min
AD215W
max
min
AD220W
max
min
Type
Fan
position
AD210W
max
min
AD215W
max
min
AD220W
max
min
8
Thermozone AD 200 W
Incoming / outgoing water temperature 90/70˚C
Incoming air temp.= +15˚C
Air flow
Output
[m
/h]
[kW]
3
1200
9,3
750
7,1
1800
14,3
1100
10,8
2400
18,6
1500
14,3
Incoming / outgoing water temperature 80/60˚C
Incoming air temp.= +15˚C
Air flow
Output
[m
3
/h]
[kW]
1200
7,7
750
6,0
1800
11,9
1100
9,0
2400
15,5
1500
11,9
Incoming / outgoing water temperature 60/50˚C
Incoming air temp.= +15˚C
Air flow
Output
[m
/h]
[kW]
3
1200
5,7
750
4,4
1800
8,8
1100
6,6
2400
11,4
1500
8,8
Incoming / outgoing water temperature 60/40˚C
Incoming air temp.= +15˚C
Air flow
Output
[m
/h]
[kW]
3
1200
4,6
750
3,6
1800
7,1
1100
5,4
2400
9,3
1500
7,2
Outgoing
Water flow
air temp.
[˚C ]
[l/s]
37
0,11
43
0,08
38
0,17
44
0,12
37
0,22
43
0,17
Outgoing
Water flow
air temp.
[˚C ]
[l/s]
34
0,09
38
0,07
34
0,14
39
0,10
34
0,18
38
0,14
Outgoing
Water flow
air temp.
[˚C ]
[l/s]
29
0,13
32
0,10
29
0,21
32
0,15
29
0,27
32
0,20
Outgoing
Water flow
air temp.
[˚C ]
[l/s]
26
0,05
29
0,04
26
0,08
29
0,06
26
0,11
29
0,08
Incoming air temp. = +20˚C
Output
Outgoing
air temp.
[kW]
[˚C ]
8,5
41
6,5
45
13,1
41
10,0
46
17,1
41
13,1
45
Incoming air temp. = +20˚C
Output
Outgoing
air temp.
[kW]
[˚C ]
7,0
37
5,4
41
10,7
37
8,2
42
14,0
37
10,8
41
Incoming air temp. = +20˚C
Output
Outgoing
air temp.
[kW]
[˚C ]
5,0
32
3,8
35
7,6
32
5,8
35
9,9
32
7,6
35
Incoming air temp. = +20˚C
Output
Outgoing
air temp.
[kW]
[˚C ]
3,8
29
3,0
32
5,9
29
4,5
32
7,7
29
6,0
32
Water flow
[l/s]
0,10
0,07
0,15
0,11
0,20
0,15
Water flow
[l/s]
0,08
0,06
0,12
0,09
0,16
0,12
Water flow
[l/s]
0,11
0,09
0,18
0,13
0,23
0,18
Water flow
[l/s]
0,04
0,03
0,07
0,05
0,09
0,07