6.5.
Batteries
Follow the instructions.
Smoking and open fire prohibited.
Live parts.
Risk of explosion. Prohibit
shortcut.
Common instructions:
Never discharge the batteries more than 80%.
Before charging the batteries: open both hoods.
Only full charge-cycles are allowed.
Weekly maintenance:
Check the electrolyte-level of the batteries.
If the level is below the sieve top up the level of the electrolyte by demineralised water up to the
lowest ring of the sieve.
Battery topped up to
late; lead-plates
vissible.
SPS - E-series_HL_1-2
Safety instructions
Top up battery now.
Wear eye-protections glasses
and protections clothing
Electrolyte is highly caustic
chemical.
Charge batteries only when
adequate ventilation is available.
Defect batteries shall be recycled.
Battery topped up
well.
Battery topped up to
much.
28/32