PR electronic 5333 Guia De Inicio Rapido página 9

Transmisor de 2 hilos programable
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation Drawing 5300Q502.
Model 5331C,5331D, 5333C and
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or
Class I, Zone 0, IIC
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
1
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
6
Terminal 3,4,5,6
Only passive, or non-energy
storing devices such as RTD's
and Thermocouples may be
connected.
Model 5335C, 5335D.
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or
Class I, Zone 0, IIC
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
1
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
6
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
5300Q502.doc
2005-12-16
Rev. AD
14
5333D
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
-
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
2
La or Lo > Li + Lcable
3
This device must not be
connected to any associated
5
4
apparatus which uses or
generates more than 250 VRMS
SENSOR
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
-
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
2
La or Lo > Li + Lcable
3
This device must not be
connected to any associated
5
4
apparatus which uses or
generates more than 250 VRMS
SENSOR
The entity concept.
1/2
5300Q502.doc
The Transmitter must be installed according to National Electrical Code
(ANSI-NFPA 70).
When installed in Class II locations the Transmitter shall be installed in an enclosure
with a specified ingress protections of IP6X according to IEC60529 and Dust-tight
conduit seals must be used.
Equipment that is FM-approved for intrinsic safety may be connected to barriers based
on the ENTITY CONCEPT. This concept permits interconnection of approved trans-
mitters, meters and other devices in combinations which have not been specifically
examined by FM, provided that the agency's criteria are met. The combination is then
intrinsically safe, if the entity concept is acceptable to the authority having jurisdiction
over the installation.
The entity concept criteria are as follows:
The intrinsically safe devices, other than barriers, must not be a source of power.
The maximum voltage Ui(V
) and current Ii(I
MAX
which the device can receive and remain intrinsically safe, must be equal to or greater
than the voltage (Uo or V
or V
) and current (Io or I
OC
t
can be delivered by the barrier.
The sum of the maximum unprotected capacitance (C
the interconnecting wiring must be less than the capacitance (C
connected to the barrier.
The sum of the maximum unprotected inductance (L
the interconnecting wiring must be less than the inductance (L
connected to the barrier.
The entity parameters Uo,V
or V
and Io,I
OC
t
provided by the barrier manufacturer.
2005-12-16
Rev. AD
), and maximum power Pi(Pmax),
MAX
or I
) and the power Po which
SC
t
) for each intrinsically device and
i
) which can be safely
a
) for each intrinsically device and
i
) which can be safely
a
or I
, and C
and L
for barriers are
SC
t
a
a
2/2
15
Tabla de contenido
loading

Productos relacionados para PR electronic 5333

Tabla de contenido