6.2 Saving the momentary value (Display-Latch)
In case of a High Signal at the Latch input, the current mea-
sured value is frozen on the display. The minimum and ma-
ximum value acquisition continues operating in the
background.
7 Troubleshooting and alarm messages
7.1 Display does not light up
If the display does not light up, check the supply voltage
or the power supply cables. Do not open the housing by
force.
7.2 Measuring rang overflow or underflow
Measuring range overflow
Ranges see 8.1
Measuring range underflow
Ranges see 8.1
7.3 Input problems
Probe broken or input signal
exceeds the allowable range
8 Main technical features
Operation:
by means of two front panel keys
DIsplay:
5-digit display, red 7-segment LED's,
Height of the figures 8 mm
Display range: (see temperature range), with leading
zeros suppression Measuring range over-
flow, indicated by ooooo on the display.
Measuring range underflow, indicated by
uuuuu on the display.
8.1 Electrical features
Input:
Thermoelement-sensor
J (Fe-CuNi)
K (Ni-CrNi)
N (NiCrSi-NiSi)
Temperature ranges:
after DIN IEC 548
J (Fe-CuNi)
K (Ni-CrNi)
N (NiCrSi-NiSi) -200,0 °C ... +1372,0 °C
Resolution:
0,1°C (0,1°F) or 1°C (1°F)
Reference point compensation:
internal or external (programmable)
Reference point error:
+/–1,0 °C typ.
+/–3,0 °C max.
Zumutbare Änderungen aufgrund technischer Verbesserungen vorbehalten.
16
Pepperl+Fuchs GmbH 68301 Mannheim Telefon (0621)776-11 11 Telefax (0621)776-27-11 11 Internet http://www.pepperl-fuchs.com
-210,0 °C ... +1200,0 °C
-346,0 °F ... +2192,0 °F
-200,0 °C ... +1372,0 °C
-328,0 °F ... +2501,6 °F
-328,0 °F ... +2372,0 °F
Linearity error:
< 0,4 % for the whole measuring range at
an ambient temperature of 20°C
Temperature drift:
0,1 K/Kambient
Measuring rate:
5 measurements/second, fixed
Display refresh:
1 ... 2 times per second
Display Latch input:
DIsplay stop for the current measured
value, active for log. 1
Switching
level
Supply voltage:
10 ... 30 V DC, electrically separated,
with Verpolschutz
Current consumption:
max. 40 mA
Test voltage:
500 Veff; 50/60 Hz; 1 min
Data backup: EEPROM
8.2 Mechanical features
Housing:
Housing for control panel 48 x 24 mm
according to DIN 43 700, RAL 7021
Dimensions: (W x H x D):
48 x 24 x 66 mm
Panel cut-out: (W x H):
45+0,6 x 22,2+0,3 mm
Mounting depth:
approximately 59 mm
Weight:
approximately 50 g
Protection level:
IP 65 (on the front side)
Connection:
Screw terminal, RM 5.08, 7 poles
Connection diameter:
single-wire
thin wire
wire dimensionsAWG 26-16
Copyright Pepperl+Fuchs, Printed in Germany
log. 0: 0 ... 2 VDC
log. 1: 4 ... 30 VDC
0,14 .. 1,5 mm2
0,14 .. 1,5 mm2