Flomec TM Serie Manual De Usuario Original página 2

Ocultar thumbs Ver también para TM Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

3. Attach meter with arrow pointed in the direc-
tion of fluid flow.
4. For NPT and BSP Fittings - Hand tighten
the meter at the housing ends. Do not use
a wrench or similar tool to tighten. This can
damage the housing.
WARNING
Compatibility of this product's material
and the process fluid and/or environment
should be considered prior to putting into
service.
WARNING
Product should never be operated outside
its published specifications for temperature
or pressure. See specifications for your
model.
WARNING
Make sure flow and pressure have been
eliminated from process pipe prior to
installing or removing product.
Terminal
Block
2
OPEN COLLECTOR SIGNAL OUTPUT
Red
1
Black
2
3
4
White
The terminal block is identified as follows:
Pin #1 6 volt square wave (not used)
Pin #2 +9 to 35 volt DC Input
Pin #3 Common Ground
Pin #4 Open Collector signal Output
Always use appropriate thread sealant or
flange gaskets when connecting product
process piping.
to
To protect against leakage, seal all pipe
threads with an appropriate sealing com-
pound. Make sure the sealing compound
does not intrude into the flow path.
NOTE: If connecting to new male pipe threads,
burrs and curls can adversely affect accu-
racy. Correct the problem prior to turbine
installation.
NOTE: Do not over tighten the flange bolts. This
may cause the gasket to be compressed
into the flow stream and may decrease the
accuracy of the meter.
Installation near high electromagnetic fields
and high current fields is not recommended
and may result in inaccurate readings.
Wiring Diagram 1
+9 to 35 volt DC
Resistor
Common
(Ground)
Open Collector
Signal
WARNING
CAUTION
CAUTION
Customer
Interfacing
Equipment

Hide quick links:

Tabla de contenido
loading

Tabla de contenido