STEP 4: Select supply / motor cables and fuses or MCB
The supply/motor cables and fuses or MCB's used should follow the ratings provided in the table below:
The voltage rating of fuses and MCBs must be greater than or equal to the highest supply voltage of
the system. Fuses: The AC supply to the drive must be installed with suitable protection against
overload. Failure to observe this requirement will cause risk of fire.
WARNING
Ground conductor size:- Either 10 mm² or two conductors of the same cross-sectional area as the input
NOTE
conductors.
Input
Model
Phases
01100017
1
01100024
1
02100042
1
02100056
1
01200017
1
01200024
1
01200033
1
01200042
1
02200024
1 / 3
02200033
1 / 3
02200042
1 / 3
02200056
1 / 3
02200075
1 / 3
03200100
1 / 3
04200133
1 / 3
04200176
3
02400013
3
02400018
3
02400023
3
02400032
3
02400041
3
03400056
3
03400073
3
03400094
3
04400135
3
04400170
3
* These fuses are fast acting.
** For UL installations, the circuit breaker must be listed under category control number DIVQ / DIVQ7, rated
600 Vac with a short circuit rating > 10 kA. In other countries, circuit breakers compliant with EN IEC 60947-2 are
recommended, with > 10 kA short circuit breaking capacity
The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current,
NOTE
when protected by fuses.
IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
NOTE
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
C200/C300 Step By Step Guide
Issue Number: 1
Fuses
UL
IEC Class
Class CC
gG
*
J, or T
A
A
10
15
16
15
20
20
25
25
6
6
6
6
10
15
16
15
6/6
6/6
10/10
10/10
16/10
15/10
20/16
20/15
20/16
20/15
25/20
25/20
25/20
25/20
25
25
6
6
6
6
6
6
6
6
10
6
10
15
16
15
16
15
20
20
25
25
MCB
IEC60364-5-52
rating**
mm²
Input
15
1
15
1.5
15
2.5
15
4
15
1
15
1
15
1
15
1
15
1
15
1
15
1
15
2.5/1.5
15
2.5
25/20
4
25/20
4/2.5
25
4
15
1
15
1
15
1
15
1
15
1
15
1
15
1.5
25
2.5
20
2.5
25
4
Cables
UL 508C
AWG
Output
Input
Output
1
16
16
1
14
16
1
12
16
1
10
16
1
16
16
1
16
16
1
16
16
1
16
16
1
16
16
1
16
16
1
16
16
1
12/14
16
1
12
16
1.5
10/12
14
2.5
10
12
2.5
10
12
1
16
16
1
16
16
1
16
16
1
16
16
1
16
16
1
14
16
1
12
16
1.5
12
14
2.5
10
12
2.5
10
12
5