Figure 4: Remote key switch wiring
RKEY
Note:
Remove the jumper installed on EXTSW only if you are
installing a remote key switch.
Figure 5: Switch and LED wiring
LED+
LED+
SW-
SW-
Switch and LED terminals are listed in Table 4 and Table 5.
Table 4: Switch terminal definitions
Terminal
Description
J7-1
ACK/Silence SW
J7-2
Reset SW
J7-3
Signal Silence SW
J7-4
Drill SW
J7-5
Lamp Test SW
J7-6 to J7-8
Not used
P/N 3100973-ML • REV 2.0 • ISS 16MAR11
SWxx
SW–
LED+
+
LEDxx
Terminal
Description
J7-9 to J7-12
SW 1 to SW 4
J8-1 to J8-12
SW 5 to SW 16
Table 5: LED terminal definitions
Terminal
Description
J1-1
Reset LED
J1-2
Signal Silence LED
J1-3
Drill LED
J1-4
Ground Fault LED
J1-5
Trouble LED
J1-6
Controls Enable LED
J1-7
ACK/Silence LED
J1-8
Lamp Test LED
J2-1
Power LED
J2-2
Fire Alarm LED
J2-3
Supervisory LED
J2-4 to J2-8
Not used
J3-1 to J3-8
LED 1 to LED 8
J4-1 to J4-8
LED 9 to LED 16
J5-1 to J5-8
LED 17 to LED 24
J6-1 to J6-8
LED 25 to LED 32
Specifications
Voltage
24 VDC
Current
Standby
36 mA at 24 VDC
Alarm
146 mA at 24 VDC
Switch inputs
Quantity
5 dedicated, 21 total
Type
Dry contact
Open collector outputs
For LED driver use only
Current
10 mA at 5.7 V input max.
Power factor
PF 1.0 (resistive)
Quantity
43
Type
Common (11), zone or programmable (32)
LED current
7 mA at 5.7 VDC per LED, typical
Power wiring
14 to 18 AWG (1.0 to 2.5 mm²)
Annunciator circuit
Class/Style
Class B, Redundant Class B, or Class A
Wire size
18 to 14 AWG (1.0 to 2.5 mm²)
Type
Twisted pair, 6 twists per ft. min.
Length
4,000 ft. (1,219 m), max.
Baud rate
9600 to 115200 baud
Remote key switch
5 VDC at 1 mA, power-limited, unsupervised
Dimensions
3.25 × 10.25 × 1.50in. (8.3 × 2.6 × 3.8 cm)
Ground fault
0 Ω
impedance
Operating environment
Temperature
32 to 120°F (0 to 49°C)
Relative humidity
0 to 93% noncondensing