Circuit board wiring diagram for Day/Night opening mode and Power Block or Day/Night and electric Lock
- 1 - MODE B -
This mode is only recommended if UPS units are installed upstream.
This mode enables manual setting by the user of a second opening width (leaving the max. opening width set by the installer on CO-02 stored in the
memory).
To select the type of opening required, use a special selector.
If interested in this operating mode, contact us for the specific instructions.
- 2 - ENERGY SAVING MODE -
USE: this mode enables variation of the opening width according to transit intensity, as set on the energy saving function CO-19.
Normal opening width is set on CO-02.
The partial opening width (energy saving) is set on CO-20.
The time for which the door remains closed is calculated and stored on CO-19.
When the door is ready to open according to the width set on CO-02 and has remained closed for longer than the time interval set on CO-19, this
means that transit is not intense and therefore the door opens to the width set on CO-20.
When the door is opened before the interval set on CO-19, the door opens completely.
Also in the case of intense transit forcing the door to remain open for an interval eight times that of the wait time before automatic closing as set on
CO-09, the opening width changes automatically to that set on CO-02 (Max. opening).
This function is enabled when the SYS is switched on (closed contact) by means of the relative switch.
If the opening/closing is activated with the SYS turned off (open contact), the door opens according to the setting on CO-02.
Circuit board connections:
Connect output sensors (INSIDE) and input sensors (OUTSIDE) to the relative terminals (CN4-CN5).
Set 1 or 2 pairs on the photocell circuit and then connect the photocells to wires 4-5 (0-LIMIT).
Connect other types of sensors and pushbuttons to wires 5-7 (0-HELP) to enable opening.
Connect a switch to wires 5-6 (0-SYS) to enable modification of door opening.
An emergency pushbutton can be fitted by connecting it to wires 8-9 (0-STOP).
A selector should also be connected to wires 3-5 (0V – D/N) to enable selection of the day/night mode.
Programmer parameter setting procedure
Turn on the power supply
Press STOP on the programmer
Press DATA-ENTER - "CO-00" appears on display
Press the up key once - "CO-01" is displayed
Press DATA-ENTER on CO-01 to enter the Options menu
Select option "2" by means of the up/down keys.
Press DATA-ENTER to confirm the selection – "CO-02" appears on display.
Press DATA-ENTER on CO-02.
Set the opening width by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected width – CO-03 appears on display.
Press the up key until CO-19 is displayed
Press DATA-ENTER on CO-19.
Set the time for which the door must remain closed before passing automatically from maximum opening width as set on CO-02 to energy saving mode
by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected time – CO-20 appears on display.
Press DATA-ENTER on CO-20.
Set the opening width in energy saving mode by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected width – CO-21 appears on display.
Press the up key until CO-39 is displayed
Press DATA-ENTER on CO-39.
Enter the door weight by means of the up/down keys (to select the specific display use key >, the selected item flashes).
Press DATA-ENTER to confirm the selected value – CO-40 appears on display.
Press RUN on the programmer.
Turn the main door switch off and on again and perform an operation check.