8. Press FORWARD to select the wanted alarm level.
9. Press ENTER to memorise.
The ventilation level 1st speed will be displayed "50ppm".
10. Press PROGRAMMING if you want to change it.
11. Press FORWARD to select the wanted alarm level.
12. Press ENTER to memorise.
The ventilation level 2nd speed will be displayed "100ppm".
13. Press PROGRAMMING if you want to change it.
The different levels will be displayed:
14. Press FORWARD to select the wanted ventilation level.
15. Press ENTER to memorise.
The ventilation input retard will be displayed "1 min". This menu allows to program a retard from the
moment the ventilation condition is detected until the ventilation acts.
16. Press PROGRAMMING if you want to change it.
17. Press FORWARD to select the wanted one -from 0 to 4 min-.
18. Press ENTER to memorise.
The ventilation output retard will be displayed "2 min". This menu allows to program a retard from the moment
the no ventilation condition is detected until it is disconnected.
19. Press PROGRAMMING if you want to change it.
20. Press FORWARD to select the wanted one -from 0 to 4 min-.
21. Press ENTER to memorised.
If 2 groups were previously chosen, proceed in the same way with group 2.
To program the other parameters: system overhaul warning, reset of system overhaul warning, reset of system overhaul,
acoustics inhibition, general reset, erasing events, detectors calibration, printing out parameters, exit the programming
menu, follow the steps described in point 5 regarding the spanish standard.
Carbon Monoxide CO
Explosives EXP
Oxygen O
2
Nitrogen Dioxide NO
2
Other toxic gases
Carbon Monoxide CO
Explosives EXP
Oxygen O
2
Nitrogen Dioxide NO
2
Chlorine CI
Ammonia NH
2
3
Other toxic gases
From 20 to 390 ppm.
From 10 to 90% L.E.L.
From 2 to 24%
From 1 to 19 ppm
From 20 to 190 ppm
From 20 to 390 ppm.
From 10 to 90% L.E.L.
From 2 to 24%
From 1 to 19 ppm
From 1 to 99
From 1 to 195 ppm