ANALOGUE INPUTS
Air / water units type 00
N
Cold only
B1
Circuit high pressure transducers
P.A.
B2
Low pressure circuit transducer
P.B.
Inlet water temperature probe
B3
(MASTER)
TIA
Evaporator common outlet water
(TUAC)
temperature probe (SLAVE !)
B4
Compressor discharge temperature
TGP
probe
B5
Evaporator outlet water tempera-
TUA
ture probe
B6
Amperometric transformer input
Master : multifunctional input
B7
Slave :
SUR
Recovery outlet temperature probe
B8
Outside air temperature probe
TAE
B9
TEV
B10
TL
B1 EXP
SIR
SFC
B2 EXP
SUR
SFC2
B3 EXP
SRU
B4 EXP
34
Air / water units other versions
Free-cooling, Total recovery, Heat
pump
Circuit high pressure transducers
Low pressure circuit transducer
Inlet water temperature probe
(MASTER)
Evaporator common outlet water
temperature probe (SLAVE !)
Compressor discharge temperature
probe
Evaporator outlet water tempera-
ture probe
Amperometric transformer input
Master : multifunctional input
Slave :
Recovery outlet temperature probe
Outside air temperature probe
Gas temperature probe
-
evaporator
-
Liquid temperature probe
Recovery inlet temperature probe
Inlet probe
-
Free-cooling coil inlet probe
(Glycol free)
Recovery outlet temperature probe
-
Free-cooling coil outlet probe
(Glycol free)
Intermediate exchanger water inlet
-
probe (Glycol free)
-
Not used
NS-NSH UNITS
Notes
4-20 mA probe type
Range 0-30 bar
4-20 mA probe type
Range 0-10 bar
Probe type NTC 10k Carel
-Only on master
- (Only on Slave1)
Probe PT1000
Probe type NTC 10k
Probe type NTC 10k
In case of use as transformer input
do not enable analogue input B6
Probe type NTC 10k
In case of use as multifunctional
input do not enable analogue input
B7
Probe type NTC 10k
Probe type NTC 10k
In case of use as potentiometer do
not enable analogue input B9
Probe type NTC 10k
Probe type NTC 10k
-On expansion
Probe type NTC 10k
-On expansion
Probe type NTC 10k
-On expansion
Probe type NTC 10k
-On expansion