Installation
Description
Connector size
Max input current
Input cable size
(∅ and neutral)
Max output current
Output cable size
(∅ and neutral)
Earth cable size
Table 7: Connection data Linear Plus
*
When in Bypass mode, the entire output current of the UPS is passed by the phase L1 and
Neutral cables. In order to simplify Table 7 no distinction has been made between phase L1 and
phases L2 and L3. The cable sizes are defined for the maximum current carried by the output
.
cables
UPS-TYPE
Connector size / mm
Max. input current / A
Input cable size (∅ and neutral) / mm
Max. output current / A
Output cable size (∅ and neutral) / mm
Earth cable size (PE) / mm
Table 8: Maximum currents and recommended cable sizes RM
Warning
Particularly sensitive equipment may be susceptible to interference, in
order to prevent this it is suggested that input, output and any external
battery cables to the UPS be housed in earthed, metal conduits or that
shielded cables be used. Routing of cables (e.g. power supplies,
communication or data lines) to other equipment, should be kept
separate from that of UPS cables.
EN-20
Unit
UPS power rating
kVA
6 - 1/1
2
mm
10
Arms
34
2
mm
6
Arms
34
2
mm
6
2
mm
6
2
rms
2
rms
2
2
User Handbook
CHLORIDE LINEAR Plus/RM
10 -1/1
10
56*
10
56*
10
10
Linear Plus
Linear Plus
RM 6 kVA
RM 10 kVA
16
30
6
29
6
6
SU59802UM01, rev.3/ Last modified: 08/2005
10 - 3/1
10
56*
10
56*
10
10
16
51
10
50
10
10