We recommend making a note of the settings, and filing this information in a safe
place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
Three phase operation (appendix D)
Step 1: Setting ds2 and ds1 for 3-phase operation
Leader (L1)
DS-8 AC input
Set
DS-7 AC input
Set
DS-6 AC input
Set
DS-5 AES
na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Leader
DS-1 Leader
As the table above shows, the current limits for each phase should be set separately
(ds8 thru ds6). Different current limits per phase can be selected.
If a panel is connected, the AC input current limit will equal the value set on the panel
for all phases.
AES can be used on stand alone units only.
The maximum charging current is the same for all devices, and should be set on the
leader
only (ds4 and ds3).
Follower (L2)
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 na
DS-4 na
DS-3 na
on
DS-2 Slave 1
off
DS-1 Slave 1
Follower (L3)
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 na
DS-4 na
DS-3 na
off
DS-2 Slave 2
off
DS-1 Slave 2
off
on
29