Macurco GD-6 Instrucciones Para El Usuario página 20

Ocultar thumbs Ver también para GD-6:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5.
Turn on the regulator to start the gas flow and wait with the gas applied continuously.
6.
With the display function turned "On", the GD-6 will show the current concentration of gas or "0" (zero) in clean air. When the
gas concentration reaches the fan relay setting (5% LEL, for example) the display will flash back and forth between "FAn" and
"5". With the display function turned "Off", the display does not show the gas concentration, but will show "FAn" as long as the
fan relay is activated.
Note: If the Fan relay does not close within 2 minutes, consider these possibilities:
a.
Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b.
Unit needs to be re-calibrated (go through recalibration and re-test).
c.
Detector is in need of servicing (return unit to factory for servicing).
d.
Detector has fan relay set to disable (OFF) or 20% LEL. Set fan relay to 5% LEL and repeat the test.
7.
Remove the gas from the sensor. Proceed to test the alarm relay or replace the top cover.
Testing the Alarm Relay
Note: The gas concentration to activate the Alarm relay depends on the setting.
Connect the 20% LEL cylinder of Combustible Gas to the regulator. Ensure that the gas used for calibration matches the gas selected
in the GD-6 configuration.
1.
Check the pressure gauge. If there is 25-psi or less the cylinder should be replaced.
2.
Place the test hood over the gas sensor. Turn on the regulator to start the gas flow.
3.
The Fan relay should activate according to the settings.
4.
With the display function turned "On" and the gas concentration reaching the Alarm Relay setting, (20% LEL, for example) the
display will flash back and forth between "ALr" and "20". The buzzer will sound indicating "Alarm" if the buzzer is turned "On".
With the display function turned off the display does not show the gas concentration, but will show "ALr" when the Alarm relay
is activated.
Note: If the Alarm relay fails to operate within 2 minutes, consider these possibilities:
a.
Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b.
Unit needs to be re-calibrated (go through recalibration and re-test).
c.
Detector is in need of servicing (return unit to factory for servicing).
d.
Detector has Alarm relay set to disable (OFF). Set Alarm relay to 20% LEL and repeat the test.
5.
Remove the gas from the sensor after test. Proceed to test the 4-20 mA output or replace the top cover.
Testing the 4-20 mA current loop
Connect the 20% LEL cylinder of Combustible Gas to the regulator. Ensure that the gas used for calibration matches the gas selected
in the GD-6 configuration.
20
Tabla de contenido
loading

Tabla de contenido