Operating
English
Function
View set point
Change set point
"Change" menu ("ro"............."tEu")
Return
"Set-up" menu ("AC" ............. "reL" )
Return
See manual for further information
List of Level 1 variables (User Level)
Variables Explanation
r0
Differential above main SETPOINT
0.2 - 10K
d0
Defrost interval (hours)
0 - 24 hours
d2
End-of-defrost setpoint.
Defrosting stops when the defrost sensor exceeds
the value,
-35 - 45 °C
d3
Max defrost duration
1 - 240 min
d7
Drip duration
At the end of defrost, the compressor and fans remain
at standstill for time d7 and the defrost LED on the
front panel flashes.
0 - 10 min
F5
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for time F5 after
dripping. This time begins at the end of dripping. If no
dripping has been set, the fan pause starts directly at
the end of defrost.
0 - 10 min
A1
Maximum temperature alarm
Allows user to define a maximum temperature for the
room being refrigerated. Above value A2 an alarm
trips: the alarm LED flashes, the displayed temperature
flashes and the buzzer sounds to indicate the problem.
A2
Maximum temperature alarm
Allows user to define a maximum temperature for the
room being refrigerated. Above value A2 an alarm
trips: the alarm LED flashes, the displayed temperature
flashes and the buzzer sounds to indicate the problem.
tEu
Evaporator sensor temperature display
(displays nothing if
dE =1)
(read only)
List of Level 2 variables (Installer Level)
AC
Door switch status
0 = normally open, 1 = normally closed
F3
Fan status with compressor off
0 = fans run continuously
1 = fans only run when compressor is working
F4
Fan pause during defrost
0 = fans run during defrost
1 = fans do not run during defrost
dE
Sensor presence
0 = evaporator sensor present
1 = no evaporator sensor
d1
Defrost type
1=hot gas, 0=electric
bdr
Modbus baudrate
(Danfoss System unit =19200 baud = 7)
AK-RC 101 / 103
Press
+
/
+
(4 seconds)
+
(4 seconds)
+
+
(4 seconds)
+
(4 seconds)
Default
2K
4 hours
15 °C
25 min
0 min
0 min
-45 °C
+45 °C
-
0
1
1
0
0
7
RI8NN55K
Instructions
© Danfoss 2015/08
Ad
Modbus address
1 ... 247
(+ setting: AU must be set to 7 + move jumper)
Ald
Minimum and maximum temperature alarm
1...240 min
C1
Minimum time between shutdown and
subsequent switching on of the compressor.
0...15 min
CAL
Correction of sensor signal
-10...+10
Pc
Compressor protection contact status
0=NO, 1=NC
doC
Compressor safety time for door switch
0...5 minutes
tdo
Restart time, if the door remains open
0... 240 min. (0=no function)
Fst
FAN shutdown TEMPERATURE
-45...+45 °C
Fd
Fan differential below Fst
0...+10K
LSE
Min. limit of set point setting
-45...HSE
HSE
Max. limit of set point setting
45... LSE
tA
NO – NC alarm relay switching
0 = activates when alarm is on
1 = deactivates when alarm is on
AU
Auxiliary/alarm relay control
0= alarm relay
1= manual auxiliary relay controlled via AUX key
2= automatic auxiliary relay managed by StA temp.
setting with 2°C differential
3= not used
4= pump-down function (see manual)
5= free voltage contact for condensing unit (AUX relay
and compressor relay in parallel)
6=Relay used to control a heating element in the
crankcase. The relay is on when the compressor is
stopped.
7=The relay function is cancelled and data
communication is permitted
StA
Temp. setting for aux. relay
-45...+45 °C
In1
Man in cold room alarm
0 = compressor protection
1 = man-in-room alarm
P1
Password type of protection
( active when PA does not equal 0)
0 = display set point only
1 = display set point, AUX, light access
2 = access to programming not permitted
3 = access to second level programming not
permitted
PA
Password
(see P1 for the type of protection), 0...999, 0=not active
reL
Software version (Read only)
0
120 min
0 min
0
0 = NO
0
0
+45 °C
2K
-45°C
45°C
1
0
0
0
3
0
-
5
loading