VSD settings for 50 Hz
MYMn
Nom volt
Nom amps
Output freq
Nom speed
Ctrl type
Base freq
Int therm prot
MIN speed
MAX speed
PID min output
PID max output
Intern ref PID
Intern ref PID
Prop gain PID
Intern gain PID
Comand Bloq func
Last error regist
5.4. VSD ERROR SUMMARY TABLE
M008 is a read only parameter, and is the reference of the last error registered by the VSD.
At the informative level it is important to review this parameter in case of FAULT.
Below is a list of possible error codes.
LFT
0 [No fault] (nOF)
2 [Control Eeprom] (EEF1)
3 [Incorrect config.] (CFF)
4 [Invalid config.] (CFI)
5 [Modbus com.] (SLF1)
6 [int. com.link] (ILF)
7 [Com. network] (CnF)
8 [External flt-LI/Bit] (EPF1)
9 [Overcurrent] (OCF)
10 [Precharge] (CrF)
11 [Speed fdback loss] (SPF)
12 [Load slipping] (AnF)
16 [Drive overheat] (OHF)
17 [Motor overload] (OLF)
18 [Overbraking] (ObF)
19 [Mains overvoltage] (OSF)
20 [1 output phase loss] (OPF1)
21 [Input phase loss] (PHF)
22 [Undervoltage] (USF)
23 [Motor short circuit] (SCF1)
24 [Overspeed] (SOF)
25 [Auto-tuning] (tnF)
26 [Rating error] (InF1)
27 [PWR Calib.] (InF2)
28 [Int.serial link] (InF3)
29 [Int.Mfg area] (InF4)
30 [Power Eeprom] (EEF2)
32 [Ground short circuit] (SCF3)
33 [3out ph loss] (OPF2)
34 [CAN com.] (COF)
35 [Brake control] (bLF)
In the event of a VSD fault, please contact S&P after-sales service, indicating the error that is displayed.
Parameter
UnS
230 V/400 V
nCr
Dep on motor
FrS
50 Hz
nSP
Dep on motor
Ctt
U/Fq
bFr
50 Hz
ItH
Dep on motor
LSP
15 Hz
HSP
50 Hz
POL
15 Hz
POH
50 Hz
PII
Si
rPI *
50
rPG
1
rIG
1
FbCd
Start/Stop
M008
VSD settings for 60 Hz
MYMn
Nom volt
Nom amps
Output freq
Nom speed
Ctrl type
Base freq
Int therm prot
MIN speed
MAX speed
PID min output
PID max output
Intern ref PID
Intern ref PID
Prop gain PID
Intern gain PID
Comand Bloq func
Last error regist
38 [External fault com.] (EPF2)
41 [Brake feedback] (brF)
42 [PC com.] (SLF2)
44 [Torque/current lim] (SSF)
45 [HMI com.] (SLF3)
49 [LI6=PTC probe] (PtFL)
50 [PTC fault] (OtFL)
51 [Internal- I measure] (InF9)
52 [Internal-mains circuit] (InFA)
53 [Internal- th. sensor] (InFb)
54 [IGBT overheat] (tJF)
55 [IGBT short circuit] (SCF4)
56 [Motor short circuit] (SCF5)
58 [Out. contact. stuck] (FCF1)
59 [Out. contact. open.] (FCF2)
64 [input contactor] (LCF)
67 [IGBT desaturation] (HdF)
68 [Internal-option] (InF6)
69 [internal- CPU] (InFE)
71 [AI3 4-20mA loss] (LFF3)
73 [Cards pairing] (HCF)
76 [Load fault] (dLF)
77 [Bad conf] (CFI2)
99 [Ch.sw. fault] (CSF)
100 [Pr.Underload.Flt] (ULF)
101 [Proc.Overload Flt] (OLC)
105 [Angle error] (ASF)
107 [Safety fault] (SAFF)
108 [FB fault] (FbE)
109 [FB stop flt.] (FbES)
Parameter
UnS
230 V/400 V
nCr
Dep on motor
FrS *
60 Hz
nSP
Dep on motor
Ctt
U/Fq
bFr *
60 Hz
ItH *
Dep on motor
LSP *
18 Hz
HSP *
60 Hz
POL *
18 Hz
POH *
60 Hz
PII
Si
rPI *
50
rPG *
1
rIG *
1
FbCd *
Start/Stop
M008
27