MANUAL DE INSTRUCCIONES
Setting the set point (desired temperature)
Press SET for 1 sec the set value will start flashing after a few moments.
‐
Increase or decrease the value using UP or DOWN.
‐
Press SET to confirm the new value.
‐
Switching the device ON/OFF
Press UP for more than 3 sec. The control and defrost algorithms are now disabled and the instrument
displays the message "OFF" alternating with the temperature read by the set probe.
Manual defrost (models S, X, Y and C only)
Press for DOWN more than 3 sec (the defrost starts only the temperature conditions are valid).
Continuous cycle (models S, X, Y and C only)
Press UP and DOWN together for more than 3 sec.
Access and setting type F (frequent) and type C (configuration) parameters
1. Press SET for 3 sec (the display will show "PS")
2. To access the type F and C parameter menu, enter the password "22"using UP/DOWN;
To access the F parameter menu only, press SET (without entering the password);
3. Scroll inside the parameter menu using UP/DOWN;
4. To display/set the values of the parameter displayed, press SET, then UP/DOWN and finally SET to
confirm the changed (returning to the parameter menu).
To save all the new values and exit the parameter menu, press SET for 3 sec.
To exit the menu without saving the changed values (exit by timeout) do not press any button for at
least 60 sec
Table of alarms
Alam
buzzer and
code
alarm relay
E0
active
E1
inactive
E2
inactive
IA
active
dOr
active
LO
active
HI
active
EE
inactive
EF
inactive
Ed
inactive
dF
inactive
cht
inactive
CHT
active
EtC
inactive
Our products have been precissely modified before leaving factory. To avoid damaging compressor unit or
other malfunctions, users must not modify the microcomputer parameters privately.
J
.P. SELECTA s.a.u.
CÓDIGO 80404 REV 0
LED
Description
ON
probe 1 error=control
ON
probe 2 error=defrost
ON
probe 3 error=condenser
external alarm
ON
open door alarm
ON
low temperature alarm
ON
high temperature alarm
ON
unit parameter error
ON
operating parameter error
ON
defrost ended by timeout
ON
defrost running
ON
condenser dirty pre‐alarm
ON
condenser dirty alarm
ON
clock alarm
ON
Autovía A-2 Km 585.1 Abrera 08630 (Barcelona) España
09/2020
Parameters
involved
‐
[d0=0/1]
[A4=10]
[A4=10][+A7]
[A4=7/8][+A7]
[AL][Ad]
[Ah][Ad]
‐
‐
[dP][dt][d4][A8]
[d6=0]
[A4=10]
[A4=10]
Tel 34 93 770 08 77 Fax 34 93 770 23 62
Pag.: 13