Samsung DVE52M775 Serie Manual Del Usuario página 15

Ocultar thumbs Ver también para DVE52M775 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Electric models
WARNING
• Your dryer has an optional cord with
an equipment-grounding conductor
and a grounding plug. This cord is sold
separately.
• The plug must be plugged into an
appropriate outlet that is properly
installed and grounded in accordance
with all local codes and ordinances.
• Do not modify the plug provided with
your dryer – if it doesn't't fit the outlet,
have a proper outlet installed by a
qualified electrician.
• If a power cord is not used and the
electric dryer is to be permanently
wired, the dryer must be connected to
a permanently grounded metal wiring
system, or an equipment grounding
conductor must be run with the circuit
conductors and connected to the
equipment grounding terminal or lead
on the dryer.
Electrical connections
Before operating or testing, follow all
grounding instructions in the "Grounding"
section. An individual branch (or separate)
circuit serving only your dryer is
recommended.
Do not use an extension cord.
Gas models – U.S. and Canada
A 120 volt, 60 Hz AC approved electrical
service with a 15-ampere fuse or circuit
breaker is required.
DV7750M-03170Y-00_EN.indd 15
Electric models – U.S. only
Most U.S. dryers require a 120 / 240 volt,
60 Hz AC approved electrical service.
Some require 120 / 208 volt, 60 Hz
approved electrical service. The electric
service requirements can be found on
the data label located behind the door.
A 30-ampere fuse or circuit breaker on
both sides of the line is required.
• If a power cord is used, the cord
should be plugged into a 30-ampere
receptacle.
• The power cord is not provided with
U.S. electric model dryers. This cord is
sold separately.
WARNING
Risk of Electric Shock
When local codes allow, you can connect
the dryer's electrical supply with a new
power supply cord kit, marked for use with
a dryer, that is U.L. listed and rated at a
minimum of 120 / 240 volts, 30-amperes
with three No. 10 copper wire conductors
terminated with closed loop terminals,
open-end spade lugs with turned up ends,
or with tinned leads.
• Do not reuse a power supply cord from
an old dryer. The power cord electric
supply wiring must be supported at the
dryer cabinet by a suitable UL-listed
strain relief.
• Grounding through the neutral
conductor is prohibited for (1) new
branch-circuit installations, (2) mobile
homes, (3) recreational vehicles, and
(4) areas where local codes prohibit
grounding through the neutral
conductor. (Use a 4-prong plug for a
4 wire receptacle, NEMA type 14-30R.)
English 15
2016-12-28
11:43:17

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Dveg52m775 serie

Tabla de contenido