Weidmuller 1238100000 Transclinic 4i+ Manual De Instrucciones página 60

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
EN
Terminal capacity section and tightening torque for the different connectors:
n
X 1, X4 String connections for measuring current (Input DC to power
board):
W ith ferrules: from 0.5 to 10 mm²; or without ferrules from
n
0.5 to 16 mm².
Tightening torque 1.2-1.5 Nm
n
Stripping length / blade size: 12 mm / 1,0 x 5,5
n
X2 (on power board):
W ith ferrules: from 0.5 to 10 mm²; or without ferrules from
n
0.5 to 16 mm².
Tightening torque 1.2-1.5 Nm
n
Stripping length / blade size: 12 mm / 1,0 x 5,5
n
X1, X3, X5, X6, X7, X8 (on CPU board):
W ith ferrules: from 0.2 to 2,5 mm²; or without ferrules from
n
0.2 to 4 mm².
Tightening torque 0.4-0.5 Nm
n
Stripping length / blade size: 7 mm / 0,6 x 3,5
n
Busbar (Output DC to power board):
Cable with M6 ring cable connector.
n
We recommend article 4R6 from Klauke GmbH (25 mm²)
Tightening torque between 4-4.5 Nm
n
F or the Transclinic 8i+ and 14i+, the same number of PV strings (for measur-
n
ing current) must be connected to both busbars. At least one PV string must
be connected per busbar.
T he final location of the device must provide sufficient fire protection in com-
n
pliance with the UNE-EN 60439-1 standard. It must also provide sufficient
mechanical support.
60
Tabla de contenido
loading

Tabla de contenido