LERBAKKEN 10, 8410 RØNDE DENMARK
Terminal (31,32)
Supply:
Voltage
Power max.
Terminal (33,34)
Status Relay:
Voltage max.
Power max.
Current max.
Terminal CH1(11,12) CH2(13,14)
Digital output:
Voltage max.
Current max.
Terminal CH1(11,12) CH2(13,14)
Relay output:
Voltage max.
Power max.
Current max.
Installation notes:
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of
at least IP54 according to type of protection Ex-n or Ex-e.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit type
9410 is allowed.
In type of protection "intrinsic safety iD" the parameters for intrinsic safety for gas group IIB are
applicable.
If the sensor circuits (Terminals 41..44, 51..54) have been installed in a type of protection other than
"intrinsic safety", the module shall not be re-installed in type of protection "intrinsic safety".
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Revision date:
2008-08-11
22
19.2 – 31.2 VDC
3 W
Non Hazardous location
125 VAC / 110 VDC
62.5 VA / 32 W
0.5 AAC / 0.3 ADC
NPN output:
30 VDC
80 mA
Non Hazardous location
250 VAC / 30 VDC
500 VA / 60 W
2 AAC / 2 ADC
Version Revision
V3 R2
Zone 2 installation
32 VAC / 32 VDC
16 VA / 32 W
0.5 AAC / 1 ADC
Zone 2 installation
32 V AC / 30 VDC
64 VA / 60 W
2 AAC / 2 ADC
Prepared by:
PB
9202QI01
Page: