The connected switching contacts must be configur
closed. The connection of two positively driven or two dependent
switching contacts must be made to the strands/pins S11 - S12 and
S21 - S22.
Connection of two
strand/pin S11 - S12 or strand/pin S21 - S22.
An external alarm LED can be connected between strand X1 and pin
X2.
Data bits
Data bit
In/Out
Activated input channel
SI-1
SI-2
SI-1 and SI-2
none
Activated alarm outputs
O-1
The code words 0000, XX00 and 00XX cause the AS-i safety monitor
to bring the installation into the safe state.
For mor e details on the ef fect of the data bits on the transmission
sequence refer to the configuration softwar e manual (see the chapter
"Monitoring devices").
Note:
If only one single-channel switch is to be connected to the module, it
is to be connected to the input SI-1. The second input SI-2 must be
bridged. This can be done by means of a wir e bridge between pin 3
and pin 4 on socket SI-1/2 or by means of a link between pin 1 and
pin 2 on socket SI-2.
7
independent switching contacts is made to
D0
D1
SI-1/O-1
SI-1
Bit sequence D3-D0
XX00
00XX
0000
XXXX
Bit sequence D3-D0
XXX1
D2
D3
SI-2
SI-2
ed as normally
X = random