5 Start Up

Reference and Run Source

The drive has a LOCAL and a REMOTE mode. The LED in the LO/RE key indicates
the drive status.
Status
The Run/ Stop command and the frequency reference are entered at the opera-
LOCAL
tor keypad.
The Run command source entered in parameter b1-02 and the frequency refer-
REMOTE
ence source entered in parameter b1-02 are used.
If the drive is operated in the REMOTE mode, make sure that the correct sources for
the frequency reference and run command are set in parameters b1-01/02 and that
the drive is in the REMOTE mode.
I/O Setup
Multi-Function Digital Inputs (H1-
The function of each digital input can be assigned in the H1-
fault setting functions can be seen in the connection diagram on
Multi-Function Digital Outputs (H2-
The function of each digital output can be assigned in the H2-
default setting functions can be seen in the connection diagram on
ting value of these parameters consist of 3 digits, where the middle and right digit
set the function and the left digit sets the output characteristics (0: Output as
selected; 1: Inverse output).
Multi-Function Analog Inputs (H3-
The function of each analog input can be assigned in the H3-
default setting of both inputs is "Frequency reference". Input A1 is set for 0 to 10V
input and A2 is set for 4-20 mA input. The addition of both input values builds the
frequency reference.
NOTICE! If the input signal level of input A2 is switched between voltage and
current, make sure that DIP switch S1 is in the correct position and
parameter H3-09 is set up correctly.
Monitor Output (H4-
Use the H4-
parameters to set up the output value of the analog monitor output
and to adjust the output voltage levels. The default monitor value setting is "Output
frequency".
20
Description
)
)
)
)
LO/RE LED
parameters. The de-
page
9.
parameters. The
page
9. The set-
parameters. The
I67E-EN
V1000 Quick Start Guide