BSP B/M/V _ _ _ - _ _ _ _ _ - P00S2B - S4(- _ _ _ )
Pressure Sensors with IO-Link
Installation (continued)
Important installation information for the front flush
sensors
NOTICE
Damage to the membrane
The membrane on the front flush sensor is very sensitive
to mechanical stresses.
► Do not touch the membrane!
–
Wait until shortly before installation to remove the
packaging and cover cap, to ensure that the
membrane is not damaged. Retain the cover cap.
–
After disassembly immediately replace the cover cap
over the membrane.
–
When installing the sensor do not use any force, since
this could damage the device and equipment.
–
Attach clamp fittings using a suitable connecting
element (e.g. half-ring or snap ring connection) per
manufacturer specifications.
Fig. 2:
Unprotected membrane on front flush sensor
Installation
Check before installation:
–
Is a seal provided which is appropriate to the measured
material and the measurement pressure?
–
Does the sealing surface of the receiving part have a
flawless surface?
–
Is any residue present on this surface?
–
Is the O-ring seated and in perfect condition in the
provided groove (for sensors with external thread and
process adapters)?
For pressure sensors with external threads do not use any
additional sealing material such as tow, hemp or Teflon
tape!
► Tighten the device by hand in the holding threads. Use
an appropriate open-end wrench to tighten and
observe the following tightening torques:
Tightening
Connection
torque
per DIN 3852
1/4"
approx.
5 Nm
1/2"
approx.
10 Nm
6
english
Membrane
Connection
NPT
per EN 837
connection
approx.
approx.
20 Nm
30 Nm
approx.
approx.
50 Nm
70 Nm
Fig. 3:
Display and connection housings rotate by 320°
Fluid
Fig. 4:
Process connection for front flush sensor
(G1/2" per DIN 3852)
Front flush sensor
Factory
connection
G1/2"