Fig. 3.c.a
fl ue
air
alternative air inlet/fumes outlet
X
min. 100 mm with back side
suction
Example of air intake from the outside, type C appliance
Fig. 3.d
3.5 Air inlet and fl ue connections
The gaSteam humidifi er is an approved type C appliance (room-sealed appliance).
The air intake pipes / fl ues should be connected according to the diagrams below.
For further requirements, see the fl ue accessories available on the market.
The air intake pipes and fl ues must be installed and positioned in compliance with the corresponding
legislation and standards in force, as well as with any national or local provisions (for example, in Italy,
the UNI-CIG 7129, UNI-CIG 7131 standards and their subsequent amendments), and therefore the
validity of the diagrams below should always be checked.
The maximum lengths indicated in the following installations have been calculated using CAREL/Ecofl am
ducting.
Four openings are available for the air intake and fl ue gas outlet (eight on the UG180):
• 2 on the top of the humidifi er (4 on the UG180);
• 2 at the rear (4 on the UG180).
The humidifi er is factory-fi tted as follows:
• fl ue gas outlet from the top of the humidifi er;
• air intake from the rear;
• supplied with an inspection section (2 for the UG180), 500 mm long.
The inspection section supplied must be assembled and the openable hole must be connected to a pipe
that acts as a condensate drain, so as to prevent condensate from causing the burner to malfunction.
Both the fl ue gas outlet and the air intake can be moved according to the installation requirements.
Element
section of linear pipe dia. 80 mm, l=1m
fl ue
section of linear pipe dia. 80 mm, l=0.5m
90° bend dia. 80 mm r=0.5 d
air
90° bend dia. 80 mm r=0.75 d
fl ue terminal dia. 80 mm
45° bend dia. 80 mm
condensate collection section dia. 80 mm
concentric terminal, dia. 80/125 mm with adapter
Flue accessories available from CAREL:
Description
1
intake terminal, dia.= 80 mm
2
80 mm extension L=1 m
3
L= 500 mm extension dia.= 80
4
90° bend dia.= 80 r 0.75 RAL9016
5
fl at tile dia.= 80 mm
inside gasket dia.= 80 mm
outside gasket dia.= 80 mm
6
condensate collection section dia.= 80 mm L=115 mm
7
vertical coaxial fl ue kit 80/125
8
fl ue terminal dia.= 80 mm
9
T joint dia.= 80 mm + cap
10 adapter for split fl ue 80/80
Other available accessories
-
inspection section dia.= 80 mm L=250 mm
-
reducer dia.= 80 D 3 INC.
-
reducer dia.= 120 mm D 5 INC
-
fl ue manifold kit D 120 for UG180
-
fl anged section dia.= 80 L= 56 mm
-
section dia.= 80 L=120 mm
-
fl anged curve dia.= 80 UG040/045
-
fl anged section
10
Fig. 3.c.b
gaSteam HARDWARE +030220538 - rel. 1.4 - 22.01.2008
pressure drop [Pa]
mbar
2
0.02
1
0.01
9
0.09
3
0.03
5
0.05
2
0.02
5
0.05
15
0.15
Code
EXHX080000
EXHP080100
EXHP080500
EXHC080080
EXHN080000
EXHQ080000
EXHU080000
EXHS0A0011
EXHK0A0000
EXHZ080000
EXHD080000 + EXHG000000
EXHA0C0000
EXHI080025
EXHR08030I
EXHR12050I
EXHM80B120
EXHL080056
EXHT080120
EXHB080060
EXHT000000
10
3
x PSI
0.29
0.15
1.31
0.44
0.73
0.29
0.73
2.18
Table 3.d