Apéndice
Ex Instrucciones
Quick Installation Guide - FM-approved MJK Ultrasonic Sensors
To MJK transmitter
Optional MJK
extension cable
p/n 690010
Notes for customer supplied materials and services
1.
Cables, fittings and conduits must be installed by the customer in accordance with NEC 501-4, 502-4 or 503-3.
2.
In Class I, II and III, Div. 1 & 2, A, B, C, D, E, F, G hazardous (classified) locations all seal fittigs, sealing com-
pounds, connections boxes, conduits, fittings, etc. must be certified and approved for use in the above men-
tioned locations.
3.
Minimum thread engagement between all threaded joints must be a maximum of 5 full threads.
4.
Interconnecting cable conduits and fittings must be grounded to a proper electrical ground. Bonding between all
conduit connections must be provided and installed by the customer as part of installation.
5.
The sensors are provided with an integral cable. An extension cable must MJK cable, part no. 690010.
6.
The cable must be run in accordance with NEC (ANSI/NFPA 70), CEC pt. I and/or applicable local code require-
ments.
7.
This installation guide is under MJK control, and modifications are not allowed without consent from the certifying
authority.
ES Shuttle Manual 100316
Class I, II and III, Div. 1 & 2,
A, B, C, D, E, F, G
hazardous location
Integral sensor cable,
see notes.
Required for Class I, II and III,
Div. 1 & 2 locations sealing fittings,
sealing cement and fiber kit.
See notes
Class I, II and III, Div. 1 & 2,
A, B, C, D, E, F, G
hazardous location
Required for Class I, II and III,
Div. 1 & 2 locations sealing fittings,
sealing cement and fiber kit.
See notes
Page 2 of 2
Denmark
www.mjk.dk
+45 45 56 06 56
Norway
www.mjk.no
+47 69 20 60 70
36
User supplied conduits
and materials, see notes.
Max. 18 inches
User supplied conduit and
connection box, see notes.
To MJK ultrasonic
sensor
The Netherlands
North America
www.mjk.com
www.mjk.com
+31 251 672171
+1 847 482 8655
Sweden
Australia
www.mjk.se
www.mjk.com
+46 53 31 77 50
+61 3 9755 1529