ELECTRICAL WIRING DIAGRAM FOR 230V USE

It is recommended that a licensed electrician install the power to your spa in accordance with the
National Electric Code and/or any local electrical codes in effect at the time of installation.
Power supply installation must include a properly rated GFCI circuit breaker. The circuit must be
dedicated and should not be shared with any other appliances. The power supply must be hard
wired into the power pack.
From the House
Breaker Box
ELECTRICAL REQUIREMENTS
230V Wiring Instructions:
4 wires/Minimum 40 amp GFCI
Breaker #8 AWG 75°C Copper Wire
Minimum (less than 100' length)
Special Note:
If the GFCI breaker trips immediately
after attempting to turn on, please
check the White Neutral Wire that is
connected to the spa.
White Neutral Wire that is connected
to Spa Neutral goes HERE.
To the Spa
10
Red
White
Black
Green