Non Hazardous Location
Associated Apparatus
Barrier or FISCO Supply
With entity Parameters
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
In each segment only one active
device , normally the associated
apparatus is allowed to provide the
necessary energy for the fieldbus
system. All other equipment
connected to the bus are not allowed
to provide energy to the system.
Separately powered equipment needs
a galvanic insulation to assure that
the intrinsic safe fieldbus circuit
remanis passive.
See Installation notes
Terminal
13,14 and 23,24
Vmax (Ui)
Imax
(Ii)
Pmax (Pi)
Ci
Li
6350QE02revAB.doc 2004-02-06
Hazardous (Classified) Location
Class I, Division 2, Group A,B,C,D
Class I, Zone 1, AEx ib IIC
Po < Pi
11,12 and 21,22
30 V
30 V
140 mA
250 mA
1 W
5.32 W
0
2 nF
0
1 µH
6350V103-ES
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
CH1
14
41
13
42
12
43
11
44
CH2
21
51
22
52
23
53
54
24
6350B
Approved
Termination
Terminal
17,5V
any
any
2 nF
1 µH
Rev. AB
Class I, Division 1, Group A,B,C,D
Class I, Zone 0, AEx ia IIC
Terminal
41-44 and 51-54
Vt or Uo
5.71 V
It or Io
8.4 mA
Pt or Po
12 mW
Ca or Co
40µF
La or Lo
200 mH
2/7
19