Figure 4: Battery Installation
and Rotary Address Switches
4 x Duracell
NOTE POLARITY
Ultra 123
1
2
+
3
+
4
ROTARY ADDRESS SWITCHES
4a
4c
Figure 5: Test Magnet Position
LINE ON BASE
TEST MAGNET
EU Declaration of Conformity
Hereby,
Life Safety Distribution GmbH declares
radio equipment types
in compliance
The full text of the EU DoC can be requested from:
D200-302-00
NOTE
Do not run more than
one
interface
time to commission
devices in an area.
+
Sensor Status LEDs
+
Sensor Status
+
Power-on initialisation
(no fault)
Fault
Un-commissioned
Sync
Normal
Idle (low power mode)
Magnet test
4b
4d
that the
52051E-RF and 52051RE-RF
are
with directive 2014/53/EU
Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy
on, the RF gateway will connect and program them with network
information as necessary. The RF sensor then synchronises with
at
a
its other associated devices as the RF mesh network is created by
the gateway. (For further information, see the Radio Programming
and Commissioning Manual - ref. D200-306-00.)
LED INDICATORS AND FAULT DESCRIPTION
The radio sensor has two LED indicators that show the status of
the device.
LED State
Long Green pulse
3 Green blinks
Blink Amber every 1s.
Red/Green double-blink every 14s
(or just Green when communicating).
Green/Amber double-blink every 14s
(or just Green when communicating).
Controlled by panel; can be set to Red
ON, periodic blink Red or OFF.
Amber/Green double-blink every 14s
1s green pulse when test magnet
activates the internal switch.
TESTING
Magnet Test
A correctly positioned test magnet will generate an alarm. Position
the magnet (M02-04-00) as shown in Figure 5, after identifying the
straight line ridge on the sensor base. To aid positioning, the sensor
LEDs will turn on green for 1s when the alarm switch activates.
Direct Heat Testing (Hair dryer of 1000-1500 watts).
Aim the heat toward the sensor from the side. Keep the heat source
about 15 cm away to prevent damage to the cover during testing.
The sensor should signal an alarm to the CIE via the Gateway
when the temperature at the sensor reaches 58°C.
Following testing, reset the alarm indication at the CIE (fire panel).
CLEANING
Use a vacuum cleaner and/or clean, compressed air to remove
dust and debris from the thermistor and sensor cover as required
(take care to avoid damaging the thermistor).
When replacing batteries, all 4 will need to be replaced
LIMITATIONS OF HEAT SENSORS
These heat sensors will only work when connected to a compatible
control panel. Heat detectors have operating limitations. They will
not sense fires where heat does not reach the sensor, and may
respond differently to varying heat conditions. Consideration must
be given to the environment when selecting and siting fire sensors.
Heat sensors cannot last forever, and we recommend replacement
after 10 years.
EN54-25: 2008 / AC: 2010 / AC: 2012 Components Using Radio
Links. EN54-5: 2000 / A1: 2002 Class A1S and A1R Heat Detectors
for use in fire detection and fire alarm systems for buildings.
Meaning
Device is un-commissioned
(factory default)
Device is commissioned
Device has an internal trouble
Device is powered and is waiting to be
programmed.
Device is powered, programmed and
trying to find/join the RF network.
RF communications are established;
device is working properly.
Commissioned RF network is in standby;
used when the gateway is powered off.
Device signals Alarm, all delays are
removed for 10 minutes.
Note
Patents Pending
0333 16
Pittway Tecnologica S.r.l.
Via Caboto 19/3, 34147 Trieste, Italy
52051E-RF DOP-IRF003
52051RE-RF DOP-IRF004
I56-3891-002