Code
No.
Name
Minimum output
C10
frequency
Maximum output
C11
frequency
Acceleration time 1
C12
Deceleration time 1
C13
Operating Mode
C14
V/f reference point
C15
C16
V
boost
min
(optimization of
torque behavior)
Frequency threshold
C17
(Q
)
min
Chopper frequency
C18
Slip compensation
C21
Current limit
C22
Accel boost
C24
Lenze 13466184 EDBSL03 v20 EN, DE, FR, IT, ES
Possible Settings
Selection
Lenze
0.0
0.0
{Hz}
50.0 7.5
{Hz}
WARNING!
Consult motor/machine manufacturer before operating above rated frequency.
Overspeeding the motor/machine may cause damage to equipment and injury to
personnel!
5.0
0.0
{s}
5.0
0.0
{s}
2
0
Linear characteristic with
Auto-Boost
1
Square-law characteristic with
Auto-Boost
2
Linear characteristic with constant
V
boost
min
3
Square-law characteristic with
constant V
boost
min
50.0 25.0
{Hz}
Set the rated motor frequency
(nameplate) for standard applications
4.0
0.0
{%}
Set after commissioning: The unloaded
motor should run at slip frequency
(approx. 5 Hz), increase C16 until
motor current (C54) = 0.8 x rated motor
current
0.0
0.0
{Hz}
2
0
4 kHz
1
6 kHz
2
8 kHz
3
10 kHz
0.0
0.0
{%}
150
30
{%}
Reference: smd rated output current
0.0
0.0
{%}
Commissioning
500
• Output frequency at 0% analog
setpoint
• C10 not active for fixed setpoints or
setpoint selection via c40
500
• Output frequency at 100% analog
setpoint
• C11 is never exceeded
999
• C12 = frequency change 0 Hz...C11
• C13 = frequency change C11...0 Hz
999
• For S-ramp accel/decel, adjust c82
• Linear characteristic: for standard
applications
• Square-law characteristic: for fans
and pumps with square-law load
characteristic
• Auto boost: load-dependent output
voltage for low-loss operation
999
40.0
500
See C08 and c17, selection 7
Reference: setpoint
• As chopper frequency is increased,
motor noise is decreased
• Observe derating in Section 2.2
• Automatic derating to 4 kHz at 1.2 x I
40.0
Change C21 until the motor speed no
longer changes between no load and
maximum load
150
• When the limit value is reached, either
the acceleration time increases or the
output frequency decreases
• When C90 = 2, max setting is 180%
20.0
Accel boost is only active during
acceleration
IMPORTANT
smd006
r
15