PIPES FOR LIGHT OIL BURNERS MODEL TBL 45LX - 75LX
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
PUMP AXIS
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
0006081324_201612
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
meters
0,5
1
1,5
2
2,5
N.B. For any missing devices in the piping,
follow existing regulations.
For each bend or valve deduct 0,25 m.
11 / 82
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
P = 3,5 m. (max.)
Total meters
H
meters
Ø i. 14
Ø i. 16
mm.
mm.
26
45
22
38
19
31
14
25
11
19
E
N
G
L
I
S
H