oventrop HydroControl M Instrucciones De Funcionamiento página 38

HydroControl M
Technical description
Fig. 2:
Dimensions side view / front view - version with internal thread
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50
2.2
Functional description
Balancing of the individual pipelines is carried out with
the presetting on the handwheel. The presetting can be
blocked using the clip located inside the handwheel (see
Fig. 3 on page 38).
Flow regulation is done by limiting the valve stroke and
hence the opening between plug and seat.
The low thread pitch allows very precise setting.
The plug position is shown on the top side of the
handwheel on a scale from 0.0 (closed) to 4.85 (fully open)
in increments of 0.05. The measuring function on the
HydroPort auxiliary valves, via a fi xed orifi ce metering
station, allows simultaneous measurement and setting.
Fig. 3:
Position of the limiting clip
1
Limiting clip
38
Abmessungen
Connection
[mm]
Rp ½
109
Rp ¾
109
Rp 1
109
Rp 1 ¼
109
Rp 1 ½
109
Rp 2
109
Änderungen vorbehalten  Alle Rechte vorbehalten
1
B
L1
[mm]
76
84
99
119
127
159
L2
H
[mm]
[mm]
147
131
152
136
161
147
176
157
180
164
199
184
1000086521_10242266 000 00
DN
Anschluss
Rp ½
15
Rp ¾
20
Rp 1
25
Rp 1 ¼
32
40
Rp 1 ½
50
Rp 2
Weight
[kg]
0.6
0.7
1.0
1.4
1.8
3.1
loading