5.3 ELECTRICAL CONNECTIONS
Create the wiring according to the voltage required by the actuator (see label on the product) following the diagram below.
Power supply 110/230 VAC
1
Blue
2
Black
3
Brown
1) Single actuator or several in parallel (NO WIFI)
1
2
3
5.4 FUNCTION TEST
Press the control button and carry out a closing procedure, checking that:
1) the window closes completely. If not, check that the overlap between panel and frame is greater than or equal to 0 mm. If
necessary, insert shims to restore the correct overlap.
2) The chain is perfectly perpendicular to the window. If necessary, adjust the connection bracket by adjusting the screws and
slots.
Once the correct closed position has been reached, press the control button and carry out an opening procedure to check that
the actuator can freely travel the entire set stroke.
Once the desired opening position has been reached, press the control button again and close. When the window is fully closed,
check that the screws, brackets and fittings are properly tightened and that the gaskets are properly compressed.
26
Neutral / Common
Phase / Opens
Phase / Closes
WIRING 230VAC ACTUATORS FOR NATURAL VENTILATION
230V~ 50/60Hz
24 VDC power supply
1
Blue
2
Brown
2) Single WIFI actuator or several actuators in parallel
without using WIFI communication
1
2
N
F
Positive
Negative
+
24 Vdc
-