5.4 Technical data table
Model
Number of elements
Max. heating capacity
Min. heating capacity
Max. heat output in heating (80-60°C)
Min. heat output in heating (80-60°C)
Max. heating capacity in DHW
Min. heating capacity in DHW
Max. heat output in DHW
Min. heat output in DHW
Efficiency Pmax (80-60°C)
Efficiency Pmin (80-60°C)
Efficiency 30%
Max. working pressure in heating
Min. working pressure in heating
Max. heating temperature
Heating water content
Heating expansion vessel capacity
Heating expansion vessel prefilling pressure
Max. working pressure in DHW
Min. working pressure in DHW
Hot water tank content
DHW expansion vessel capacity
DHW flow rate Dt 30°C
DHW flow rate Dt 30°C
Protection rating
Power supply voltage
Electrical power input in heating
Electrical power input in DHW
Empty weight
Combustion chamber length
Combustion chamber diameter
Pressure loss on fume side
52
EN
ATLAS D ECO 30/42 K 100/130 UNIT
ATLAS D ECO 30 K 100 UNIT
no.
3
kW
26.6
kW
21.1
kW
25.0
kW
19.9
kW
26.6
kW
21.0
kW
25.0
kW
20.0
%
93.9
%
94.9
%
98.2
bar
3
bar
0.8
°C
110
liters
21
liters
10
bar
1
bar
9
bar
0.1
liters
90
liters
4
l/10min
195
l/h
750
IP
X0D
V/Hz
230/50
W
195
W
195
kg
225
mm
350
mm
300
mbar
0.11
cod. 3541Q564 - Rev. 01 - 11/2022
ATLAS D ECO 42 K 130 UNIT
3
39.4
21.0
37.1
20.1
39.4
21.0
37.0
20.0
94.0
95.5
97.4
3
0.8
110
26
10
1
9
0.1
117
3
250
850
X0D
230/50
195
195
265
450
300
0.35
(Qn)
(Qn)
(Pn)
(Pn)
(PMS)
(tmax)
(PMW)
(W)
loading

Este manual también es adecuado para: