TROUBLESHOOTING
2 TROUBLESHOOTING
?
N O T E
(o): Option configurable from Unit controller. This alarm will be displayed if the system has been configured.
•
o: Default. This alarm will be displayed in the Unit controller.
•
•
–: No applicable.
2.1 ALARM CODE INDICATION ON REMOTE CONTROL SWITCH
2.1.1 Alarms for Indoor units
Retry
Alarm
YUTAKI
Stop
Code
S/SC/H/HC
Code
3
-
o
10
-
-
11
-
o
12
-
o
13
–
o
14
–
o
15
-
(o)
16
-
(o)
17
-
(o)
18
-
(o)
19
-
o
25
-
(o)
26
-
o
33
-
o
-/-/-/
34
-
o
o
-/-/
/
40
-
o
49
PMML0626 rev.0 - 07/2022
Alarm
indication
Alarm code
YUTAKI
Origin
M/HS
o
Communication
o
Indoor
o
Indoor
o
Indoor
o
Indoor
o
Indoor
(o)
Indoor
(o)
Indoor
(o)
Indoor
(o)
Indoor
o
Indoor
(o)
Indoor
o
Indoor
-
Mirror Module
-
Mirror Module
o
Indoor
Detail of Abnormality
Transmission Alarm (Not outdoor unit
detected)
2n DHW thermistor anomaly
Water inlet thermistor abnormally
(THMwi)
Water outlet thermistor abnormally
(THMwo)
Indoor Liquid Pipe Temp Thermistor
Abnormality (THMl)
Indoor Gas Pipe Temperature
Thermistor Abnormality (THMg)
Water Circuit 2 thermistor abnormally
(THMwo2)
Water DHW thermistor abnormally
(THMdhwt)
Auxiliary sensor 2 thermistor
abnormally (THMaux2)
Auxiliary sensor 1 thermistor
abnormally (THMaux1)
Water Plate HEX pipe thermistor
abnormally (THMwohp)
Auxiliary sensor 3 thermistor
abnormally (THMaux3)
Water pressure sensor (WPS)
abnormality
Water inlet thermistor anomaly
(THMwi)
Water outlet thermistor anomaly
(THMwo)
Incorrect LCD setting
Main Factors
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Loose, disconnected, broken or short-
circuited connector
Current LCD configuration does not
allow proper operation