Friedrich DDC1 Dry Contact Manual De Instrucciones página 11

Idiomas disponibles

Idiomas disponibles

3. Setting of 'SETTING_SW'
■ Using 'SETTING_SW' , select the Option of control Function
as described below
<SETTING_SW Function>
WIND Signal
No.
en/disable
0
Disable
1
Disable
2
Disable
3
Disable
4
Disable
5
Disable
6
Disable
7
Disable
8
Enable
9
Enable
A
Enable
B
Enable
C
Enable
D
Enable
E
Enable
F
Enable
1) Enable CN_WIND signal – Amount of wind flow (Low, Middle, High) signal enable
2) Enable Thermo ON/OFF input signal
- Desired Temperature 64 °F in cooling mode
- Desired Temperature 86 °F in heating mode
- No function in FAN mode
3) Enable CN_MODE signal – Operation mode (Cool, Heat, Fan) signal enable
4) Enable Thermostat priority control mode – Indoor's remote-controller signal will be disregarded
Notes
• Information of 'SETTING_SW' is sensed only initial step by Dry contact module therefore , once the
configuration changed, Reset of Dry contact module is required.
• After power input or unit's reset, wait 25~30 sec(Display LED 10 times blinking) for unit stabilization
then Dry contact module will operate normally.
CN_Ther/Oper
CN_MODE
CHANGEOVER_SW
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Thermal
en/disable
Disable
Disable
Disable
Disable
Enable
Enable
Enable
Enable
1)
Disable
Disable
Disable
Disable
Enable
Enable
Enable
Enable
CN_WIND
SETTING_SW
SETTING_SW
Oper Mode
en/disable
Disable
Disable
Enable
Enable
2)
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Setting and using method
Dry Contact Control
Priority
Disable
Enable
3)
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Installation manual 11
4)
loading

Productos relacionados para Friedrich DDC1 Dry Contact