Indicador universal para entrada proceso y temperatura
Ocultar thumbs Ver también para JR-P:
Idiomas disponibles

Idiomas disponibles

Process input
SCAL
tEAC
InP1
0000
dSP1
0000
00.00
InP2
0000
dSP2
0000
FiLt
0
Temperature input
FiLt
0
SERIE KOSMOS
When programmed input type is process, for both display scaling
"SCAL" and "tEAC" methods, parameters to be sequentially introduced
are identical.
It only must be considered that in "SCAL" method, all values must be
manually introduced through the three frontal keys whereas in "tEAC"
method, input signal value must be present at the conector at each
point that is intended to be configured.
FIRST POINT INPUT AND DISPLAY VALUE:
InP1:
Input value indication.
0000:
Value entering in counts within available model display range.
dSP1:
Display value indication.
0000:
Value entering in counts within available model display range.
DECIMAL POINT:
00.00:
Setting of decimal point position.
(Decimal point can be located in any position, and will be
the same for Display 1 and Display 2. This position remains
fixed for all configuration steps and also for RUN mode).
SECOND POINT INPUT AND DISPLAY VALUE:
InP2:
Input value indication.
0000:
Value entering in counts within available model display range.
dSP2:
Display value indication.
0000:
Value entering in counts within available model display range.
PONDERATED AVERAGE FILTER:
FiLt:
Configurable 0 to 9.
When programmed input type is temperature, for thermocouple and Pt100 or
Pt1000 sensor, the only parameter to configure is the filter and its configuration
is done in the same way as described for process input.
Display scaling is not available for this input type, the unit then will assume a
fixed calibrated range depending on sensor type and previously configured units
resolution.
www.ditel.es
JR-P / JR20-P
Value Fc (Hz)
Value
Fc (Hz)
0
--
5
1
7.3
6
2
5.1
7
3
3.8
8
4
2.9
9
2.2
1.6
1.1
0.5
0.2
60