Process
ProC
-U-
10U
200U
Temperature
tEMP
tC
-1-
-4-
1ºC
0.1ºC
DISPLAY OFFSET :
Configurable value:
-9.9 to +9.9 display counts if a tenths of degree resolution is selected
-99 to +99 display counts if a degree resolution is selected
Usually it will not be necessary to introduce any offset value, except in cases where a
known difference between temperature captured by the sensor and real temperature
should be compensated.
Potentiometer
Pot
SERIE KOSMOS
The parameters to be configured in input process
submenu are:
-A-
Pt1
Pt2
1ºF
0.1ºF
No additional configuration is needed for this input type (direct validation).
www.ditel.es
JR-P / JR20-P
INPUT TYPE:
V DC: ±10V or ±200V (-tachometric dynamo-)
A DC: ±20mA (single range, direct validation)
The parameters to be configured in input
temperature submenu are:
SENSOR TYPE:
tC:
Termocouple J(1), K(2), T(3) or N(4)
Pt1: Pt100 sensor (direct validation)
Pt2: Pt1000 sensor (direct validation)
RESOLUTION TYPE:
1ºC:
Celsius degrees
0.1ºC: Tenths of degree Celsius
1ºF:
Fahrenheit degrees
0.1ºF: Tenths of degree Fahrenheit
57