Care should be taken to avoid starting pump with high viscosity cold oil leading to pump and coupling damage. For
this reason, the T and TA pump body includes a drilling to accept an electric preheater. This drilling has been located
to give maximum heat transfer from the heater to the oil in the pump without there being direct contact between the
heater cartridge and the oil. Heaters should be connected for a period of time prior to starting the pump. When the
right temperature is reached, they can be switched off or left permanently switched on to maintain fluid oil in the
pump during the periodic burner shut-downs. The oil supply, pipes and filters must be separately heated.
Note : The bypass plug inserted beween high pressure and shaft seal is only intended to change the pump rotation,
check the presence of this plug with a 4 mm Allen key in the pressure outlet of the pump.
Caution : changing the direction of pump rotation involves changing of all pump connections.
IDENTIFICATION
(Not all model combinations are available
Consult your Suntec representative)
T
2
Preheater
facility
Revision number
PREHEATING FACILITY
PUMP SUNTEC T TECHNICAL DATA
PUMP
type
T :
Gear set capacity
(see pump capacity curves)
Shaft rotation
(seen from shaft end)
A :clockwise rotation
C : anti clockwise rotation
A
10
6
420010310000 Multiflam 1500.1 - 1800.1 PR/PR
Oil under suction
Oil under pressure
Vacuum or
Pressure
inlet pressure
gauge port
gauge port
Intake
from Tank
Plug inserted between
high pressure and shaft seal
regulating valve
Intake from Tank
31
To
pressure
regulating
valve
To
pressure
EN