Cautions, Warnings and Instructions
®
UL
File: E251034
UL61800-5-1
CSA C22.2 No 274
Electrical ratings
Model – 400 V range
Frame size
Model number
1A
RAMO5
Frame size 1A = no external fan fitted.
Input voltage 380 - 480/277 V AC, 50/60 Hz
Output voltage 380 - 480 V AC, 50/60 Hz
Short circuit rating
Model
RAMO5
RAMO5-…-xxxRxx
(with repair switch)
NOTICE
Suitable for use on a circuit capable of delivering not more than 100 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When protected by J class fuses rated 30 A.
Suitable for use on a circuit capable of delivering not more than 10 000 rms
symmetrical amperes, 480 volts maximum. Suitable for motor group
installation. When protected by a circuit breaker having an interrupting rating
not less than 10 000 rms symmetrical amperes, 480 volts maximum, rated 32 A.
– Wiring terminals marked to indicate proper connections for the power
supply, load and control circuit.
– Use 60/75 °C copper field wiring conductors.
– The ground terminals are marked with “G”, “GR”, “GRD”, “Ground”,
“Grounding”, “PE”, or the like. The symbol 5019. IEC publication 417,
may be used, but if used alone the symbol shall be defined in the
installation instructions provided with the equipment.
12/12
EU: Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
UK: Eaton Electric Ltd., P.O. Box 554, Abbey Park, Southampton Road, Titchfield, PO14 4QA, United Kingdom
Input
Output
(3-phase)
(3-phase)
FLA
FLA
6.6
6.6
Short circuit rating (kA)
Fuses
Breakers
(J-Type)
(Type C)
100 kA
10 kA
10 kA
10 kA
General
– These devices are enclosed type AC motor starters incorporating
semiconductor switching means.
– These devices are intended for installation on industrial machines in
accordance with Standard for Industry Machinery NFPA79.
– These devices do not provide reduced voltage starting feature.
– These devices do not provide isolation (isolating function).
– These devices do provide motor overload protection with thermal memory
and phase-loss protection.
– These devices or control units have not been evaluated as providing a safety
or limiting feature.
– These devices are for installation in overvoltage category III and
pollution degree 3.
– Auxiliary control outputs intended to device resistive load.
BCP Fuse/Breaker
Power
Power
A
kW
HP
3
3.0
30
Environmental ratings
– Maximum ambient air temperature: 55 °C
– Enclosure type 12
WARNING
The opening of the branch-circuit protective device may be an
indication that a fault has been interrupted. To reduce the risk of fire
or electric shock, current-carrying parts and other components of the
controller should be examined and replaced if damaged.
For Canadian installations
AVERTISSEMENT
L‘ouverture du dispositif de protection de la dérivation peut signifier
qu‘un courant de défaut a été interrompu. Pour réduire le risque
d‘incendie ou de choc électrique, les pièces porteuses de courant
et autres composants du contrôleur devraient être examinées et
remplacées s‘ils sont endommagés.
USA:
Eaton.com/contacts
Eaton.com/eatoncare
Eaton.com/aftersales
+1 877-386-2273
Eaton.com/documentation
© 2020 Eaton Industries GmbH
05/21 IL034092ZU
Eaton.com/recycling