If the door units are confi gured as secondary, but each one must call a different group of users, the following
steps can be performed:
Access to advanced confi guration by setting both the two rotary dip-switches to position '9' (the yellow
led turns on);
Set the ID dip-switch of the call module with the apartment station code that will be associated to the
fi rst button (offset);
The offset code can only be included between 0 and 31
Change the position of AUX dip-switch no. 5 (the call module emits a confi rmation tone);
Set again the AUX dip-switch no. 5 in its previous position (the call module emits a confi rmation tone);
Set again the ID dip-switches in their previous position;
Exit from the advanced confi guration, by setting again the two rotary dip-switches in the positions used
to program the door lock release time and the guaranteed conversation time: the yellow led turns off.
Example:
The secondary call module "A" only calls users form 0 to 10 and the "B" only users from 11 to 18.
On the call module "B" access to advanced confi guration;
Set the ID dip-switch to 11;
Move the AUX dip-switch no. 5;
Set again all the dip-switches in their previous position;
Exit from the advanced confi guration.