TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having positioned
the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7, DL8 and
DL9.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL6
OFF
Stop button malfunction (if Stop is not connected, perform
the jump between COM A+ and STOP).
DL7 or DL8
OFF
Faulty photocells (In case the edge is not connected, carry
out jumper between COM A+ and PHOTO 1/PHOTO 2)
DL9
OFF
Faulty safety edge (In case the edge is not connected, carry
out jumper between COM A+ and EDGE)
LED DL13 (BLUE)
ON
Some functions are enabled via smartphone, so via
smartphone check the card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause
of the fault.
EVENT
Dip 1 ON (hold-to-run mode)
Or failure of a safety device
Dip 2 ON (stroke programming)
Programming sequence stopped due to intervention of a safety
device
EVENT
No transmitter code entered
Dip 1 > 2 - transmitter code programming for full opening
Dip 1>2> 3 - transmitter code programming for R-AUX relay
Correct transmitter codes programming for opening and R-AUX
relay
Remote control code not present in memory
Memory saturated by remote control codes (1000 codes saved)
Radio code deletion for opening and R-AUX relay
EVENT
Stop button pressed
Photocell intervention
Edge intervention
Failure of a safety device or safety device engaged for too long
Alarm from edge
Failed photocells auto-test alarm
Functional block activated by smartphone
Achievement of set cycles
Energy saving activated by smartphone
Alarm - no limit switches reached or unlocked barrier
TABLE SUMMARISING VISUAL AND SOUND ALARMS
SIGNALS DURING PROGRAMMING SEQUENCE
BUZZER STATUS
Off
Off
10 seconds tone with 2 seconds pause
BUZZER STATUS
Off
Off
Off
1 Tone
Off
Off
2 Tones
WARNING SIGNALS DURING OPERATION
BUZZER STATUS
Off
1 Tone
2 Tones
Off
2 Tones every 5 seconds for 1 minute
(It is renewed by giving a command)
4 Tones every 5 seconds for 1 minute
(It is renewed by giving a command)
Off
6 Tones every 5 seconds
(It is renewed by giving a command)
Off
5 Tones
43
FLASHER STATUS
Off
Flashes on-off 250 ms
Off
Flashes on-off 500 ms
Off
On steady
FLASHER STATUS
Off
Flashes intermittently red/green
Off
Flashes red for 10 seconds
Off
Flashes orange for 10 seconds
Off
Turns green once
Off
Turns red once
Off
Runs 6 green flashes
Off
Runs 2 green flashes
FLASHER STATUS
LED STATUS AND SIGNAL OUTPUT
Off
Led DL6 turns off
Off
Led DL7-8 turns off
Off
Led DL9 turns off
Off
Led DL1 flashes on-off 250 ms
Enabled for 1 minute
No led combined
Off
No led combined
Off
Led DL12 is steady on green.
Off
No leds matched
Off
Blue led flashes once every 5 seconds
Enabled for 1 minute
No leds matched
DL1 LED STATUS
DL12 LED STATUS
G
B
loading

Este manual también es adecuado para:

Rapid s metalRapid sAa50131Aa50132