ECONCEPT TECH 25 C - 35 C
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.
Sliding Temperature
When the optional external probe is installed, the boiler adjustment system works with
"Sliding Temperature". In this mode, the temperature of the heating system is controlled
according to the outside weather conditions, to ensure high comfort and energy saving
throughout the year. In particular, the system delivery temperature is decreased as the
outside temperature increases, according to a specific "compensation curve".
With Sliding Temperature adjustment, the temperature set with the heating buttons (de-
tail 3 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set
a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. Possible
adjustments can in any case be made by the user to improve comfort.
Compensation curve and curve offset
Press the reset button (detail 6 - fig. 1) for 5 seconds to access the "Sliding temperature"
menu; the display shows "CU" flashing.
Use the DHW buttons (detail 1 - fig. 1) to adjust the curve from 1 to 10 according to the
characteristic. By setting the curve to 0, sliding temperature adjustment is disabled.
Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display
shows "OF" flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust the parallel curve
offset according to the characteristic (fig. 6).
Press the reset button (detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temper-
ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
OFFSET = 20
90
10
9
8
7
85
6
80
5
70
4
60
3
50
2
40
1
30
20
fig. 6 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
A
justments are managed according to that given in table 1.
Table. 1
Heating temperature setting
DHW temperature adjustment
Summer/Winter Switchover
Eco/Comfort selection
Sliding Temperature
OFFSET = 40
90
10
9
8
7
85
80
70
60
50
40
30
20
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer mode has priority over a possible Remote Timer Control
heating demand.
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the eco/com-
fort button (detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition it is possible
select one of the two modes with the eco/comfort button (detail 7
- fig. 1) on the boiler panel.
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature
has priority.
cod. 3540R812 - Rev. 07 - 02/2015
Water system pressure adjustment
The filling pressure read on the boiler water gauge with the system cold must be approx
1.0 bar. If the system pressure falls to values below minimum, the boiler stops and fault
F37 is displayed. Bring it to the initial value by means of the filling cock detail 1 fig. 7. At
the end of the operation always close the filling cock.
Once the system pressure is restored, the boiler will activate the 120-second air venting
cycle indicated on the display by FH.
3. INSTALLATION
3.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSON-
NEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL
MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NA-
TIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.
3.2 Place of installation
The combustion circuit is sealed with respect to the place of installation room, therefore
the unit can be installed in any room. However, the place of installation must be ade-
6
5
4
quately ventilated to prevent the creation of dangerous conditions in case of even small
gas leaks. This safety regulation is laid down by EEC Directive no. 2009/142 for all gas
3
units, including those with sealed chamber.
2
The unit is suitable for operation in a partially protected place in conformity with EN 297/
1
A6, with minimum temperature -5°C. If equipped with the special antifreeze kit, it can be
used with minimum temperatures to -15°C. The boiler must be installed is a protected
place, e.g. under the slope of a roof, inside a balcony or in a sheltered recess.
The place of installation must in any case be free of dust, flammable materials or objects
or corrosive gases.
The boiler is arranged for wall mounting and comes standard with a hooking bracket. The
wall fixing must ensure a stable and effective support for the generator.
If the unit is enclosed in a cabinet or mounted alongside, a space must be pro-
A
vided for removing the casing and for normal maintenance operations
3.3 Plumbing connections
Important
B
The safety valve outlet must be connected to a funnel or collection pipe to pre-
vent water spurting onto the floor in case of overpressure in the heating circuit.
Otherwise, if the discharge valve cuts in and floods the room, the boiler manu-
facturer cannot be held liable.
B
Before making the connection, check that the unit is arranged for operation with
the type of fuel available and carefully clean all the system pipes.
Carry out the relevant connections according to the diagram in fig. 8 and the symbols
given on the unit.
A
1
82.5
76
A = ECONCEPT TECH 25 C - B = ECONCEPT TECH 35 C
1 = System delivery - 2 = DHW outlet
3 = Gas inlet - 4 = Cold water inlet
5 = System return - 6 = Safety valve drain
fig. 7 - Filling cock
B
2
3
4
1
5
6
54 51 80.5 56
97
94
fig. 8 - Plumbing connections
2
3
4
5
6
54 51 80.5 73.5
41
EN