Electrical connection (fig. 4a)
Before connecting the device to the mains make sure that:
- the voltage and frequency rated on the data plate conform to those of the mains supply;
- an all pole circuit breaker which leaves at least 3 mm between the contacts has been installed
between the device and the mains;
- the high voltage 230V wires pass through the holes marked "A" and are routed separately
from the low voltage wires which pass through the holes marked "B";
- the wires are fastened down using a cable clamp;
- once the wiring is complete the holes through which the wires have passed have been sealed
using silicon;
- the holes which are not used are blocked by inserting the caps "C".
Terminal board connections (fig. 5)
Caution: only low voltage circuits may be wired to the external circuit binding posts 8...16.
1-2
Power supply 230Vac 50-60 Hz
3-4-5 Output for 1 motor 600 W Close-Open-Common
6
Motor earth wire
7
Power supply earth wire
8-9
Photocell power supply 24 Vac (max. 100 mA)
Opening button input "TA" (N.O. contact)
10
Closing button input "TC" (N.O. contact)
11
12
Stop button input "TB" (N.C. contact)
13
Common for all inputs
14
Security device input "FTC" (N.C. contact) with inversion during closing
15
Antenna pole
16
Antenna ground