Cycle time setting
This menu is displayed only if parameter "Typ" (#26) is equal
to "bp".
Use minus
and plus
The setting is validated with validation key
Default value: 10 minutes
Proportional Band
This menu is displayed only if parameter "Typ" (#26) is equal
to "bp".
Use minus
and plus
value.
The setting is validated with validation key
Default value: 2°C
First parameter of H&C signal: width of death band
This menu is displayed only if parameter "Mod" (#07) is equal
to "Aut" or "Aut" is selected in "Reversible" mode menu.
This parameter corresponds to width of death band.
Use minus
and plus
The setting is validated with validation key
Default value: 1°C
Second parameter of H&C signal: time threshold
This menu is displayed only if parameter "Mod" (#07) is equal
to "Aut" or "Aut" is selected in "Reversible" mode menu.
This parameter corresponds to a time threshold.
Use minus
and plus
validated with validation key
Default value: 1H
Minimum value of setting range of the set point
temperature
Default value: 5.0°C
Maximum value of setting range of the set point tem-
perature
Default value: 30.0°C
keys to set cycle time value.
Other values: [10 15 30 45 60]
keys to set proportional band
Value range: 2°C to 5°C
keys to set value.
Value range: 0°C to 5°C by step of 0.5°C
keys to set value. The setting is
.
Other values: no, 30', 2H, 3H, 4H and 5H
Value range: 5.0°C to 15.0°C
Value range: 20.0°C to 37.0°C