Drain Pipe; Electrical Wiring; General Check - Hitachi RPI-16.0FSN3PE Manual De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15

5 Electrical wiring

4.3 REQUIRED MULTI KITS
The following multikits (sold separately) are necessary to interconnect piping between outdoor and indoor unit:
(Picture for illustrative purpose only)

4.4 DRAIN PIPE

For condense draining (2 locations), prepare a polyvinyl chloride
pipe with a Ø25mm. OD (outer diameter).
Fasten the field supplied pipe to the Drain Hose with adhesive.
The drain piping should be performed with a down-slope pitch of
1/25 to 1/100.
Connect a syphon, as shown at the figure below.
>75 mm
Slope 2%
5 ELECTRICAL WIRING

5.1 GENERAL CHECK

Make sure that the following conditions related to power sup-
ply installation are satisfied:
-
The power capacity of the electrical installation is large
enough to support the power demand of the indoor unit.
-
The power supply voltage is within ±10% of the rated volt-
age.
-
The impedance of the power supply line is low enough
to avoid any voltage drop of more than 15% of the rated
voltage.
Following the Council Directive 2004/108/EC, relating to elec-
tromagnetic compatibility, the table below indicates the Maxi-
mum permitted system impedance Z
of the user's supply, in accordance with EN61000-3-11.
Indoor unit
RPI-16.0FSN3PE
RPI-20.0FSN3PE
7
PMML0323A rev.2 - 06/2014
All manuals and user guides at all-guides.com
Keep Electrical Box and Drain Pipe connection free of refrigerant
pipes.
It is very important the syphon installation in order to guarantee
the proper condensate draining.
Plug
at the interface point
max
Z
(Ω)
max
1~
0.44
1~
0.40
Indoor Unit
Multikit reference
RPI-16.0FSN3PE
E162SN3
RPI-20.0FSN3PE
E242SN3
N O T E
C A U T I O N
The status of Harmonics for each model, regarding compli-
ance with IEC 61000-3-2 and IEC 61000-3-12, is as follows:
Status regarding compliance with IEC
61000-3-2 and IEC 61000-3-12
Equipment complying with IEC 61000-3-12
Check to ensure that existing installation (mains power switch-
es, circuit breakers, wires, connectors and wire terminals) al-
ready complies with the national and local regulations.
Models
RPI-16.0FSN3PE
RPI-20.0FSN3PE
Tabla de contenido
loading

Este manual también es adecuado para:

Rpi-20.0fsn3pe

Tabla de contenido