Hitachi RPI-16.0FSN3PE-f Manual De Instalación Y Funcionamiento página 13

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
UNITS INSTALLATION

Suction Air Filter Servicing
Filter maintenance could be performed from right or left side of
the unit.
Remove filter support (x2 screws / each support) and pull out the
filter from the handle.
In those installations where the servicing space is narrow, the
filter could be bent (in three pieces) when pulling it out.
3.1.3 Fan Performance Curve
RPI-16.0FSN3PE(-f)
100
Airflow (m
Fan Speed Static Pressure
HSP (Std. Factory Setting)
LSP
HSP: High Static Pressure
LSP: Low Static Pressure
3.1.4 Static Pressure Setting
RPI units have been provided by two static pressure levels
regulation depending on the installation requirements:
High static pressure (Std. Factory Setting) and low static
pressure connectors are available into the Electrical Box.
Setting of static pressure shall be made by changing the Fan
Unit connector.
5
PMML0323A rev.5 - 05/2016
120
140
160
/min)
3
Hi
Med
Low
v1
v1
v3
v2
v2
v4
Air Filter Support
Removing Direction
Air Filter
RPI-20.0FSN3PE(-f)
120
140
Airflow (m
/min)
3
?
N O T E
When design a duct, check to ensure that the Air volume is within
working range as indicate "Fan Performance Curve".
If the Air volume is set outside working range, water-carry-over (drop
in the ceiling or into the room), noise increases, fan motor damaged
(high temperature), insufficient Cooling/Heating capacity, phenomena
can occur.
Therefore design ducts and select the correct fan speed in order to
keep the unit running in the accepted working range.
!
C A U T I O N
The static pressure setting must be the same in both units.(There are 2
Electrical boxes, so connector change must be made in both of them).
160
180
Tabla de contenido
loading

Este manual también es adecuado para:

Rpi-20.0fsn3pe-f

Tabla de contenido