4. Take special care to keep the ventilation inlets /outlets free from obstruction.
Cleaning with a soft brush followed by a compressed air jet will usually be sufficient
to ensure acceptable internal cleanliness.
5. Wear eye protection when carrying out cleaning.
Repairs
1. Only an authorized service centre should repair the generator.
Trouble
Engine will not start
AC power supply-
No electrical output
DC power supply-no
electrical output
Repeated circuit
breaker tripping
Troubleshooting
Possible cause
1. low on fuel/oil content
2. ignition switch in ''off''
position
3. faulty spark plug
4. choke in wrong position
5. unit loaded during start-up
6. spark plug wire loose
7. unit may be flooded
8. old fuel
1. faulty receptacle
2 .faulty power cord
1. circuit breaker kicked out
(DC only)
1. overload
2. faulty cords or equipment
3. Incorrect cables used.
4. mixed polarity
Suggested remedy
1. add fuel/oil mix
2. turn to ''on'' position
3. replace spark plug
4. adjust choke accordingly
5. remove load from unit
6. Attach wire to spark plug.
7. Leave the generator rest
for 5-10 minutes and then try
again, following the
instructions when doing so.
Alternatively if the choke
lever is in full choke position
(start), switch the choke to
the run position and try to
re-start.
8. remove the existing fuel
and replace with new
1. have service centre
replace receptacle
2. Replace cord.
1. Yes-Depress the reset
button, to rest the circuit
breaker.
1. reduce load
2. Check for damaged,
bare, or frayed wires on
equipment. Replace.
3. Check to make sure you
are using the DC Cables
could result in the crossing
over of polarity,
4. Check to make sure that
the DC cables are
connected to the correct
battery polarity terminals.