DEVICE PAIRING AND UNIT ADJUSTMENT USING THE DLM CONFIG APP
The DLM Config App is available for both iOS
The app provides the ability to pair various devices in a room. Additionally, you can modify load binding and edit various DLM
parameters for each device, and update the firmware in each device.
For details on the features and operation, download the DLM Config App User Guide from the
wattstopper web site at :https://www.legrand.us/wattstopper.aspx
Plug n' Go supports the most energy efficient control strategy. A set of wireless scenes are automatically assigned for load control by
switches and sensors, after pairing is complete.
NOTE: LMCS-100 software, version 4.7 or later can also be used to pair devices and edit DLM parameters. However, LMCS-100
requires use of an LMBR-650.
Load Selection Procedure
In situations in which there is more than one LMRC-611MCC in a room, the configuration
button allows access to Push n' Learn™ (PnL) technology to change the binding
relationship between the LMSW-605/LMDM-601 and loads.
NOTE: PnL cannot be used to change the binding on wireless sensors, although it is
possible to enter PnL mode from a sensor.
Step 1 Enter Push n' Learn
Press and hold the Config button (on any DLM device) for 3 seconds.
The red LED on the LMRC-611MCC begins to blink. The LED on all switches and sensors
in the local room network will also blink red. The LEDs will continue to blink until you exit
PnL mode.
NOTE: If a switch or sensor is currently "asleep", it will not blink. To ensure the switch is currently awake before initiating PnL, press its
Config button first, or initiate PnL from that switch.
All loads in the room turn OFF immediately after entering PnL, then one load will turn ON. This is Load #1. On the LMRC-611MCC for
that load, the blue Load LED will also be ON.
Step 2 Load selection
Press and release the Config button to step through the loads connected to the DLM Local Network. Each time you press the Config
button, the next load in the series will turn ON along with its Load LED, and the previous load will turn OFF.
To view the current status of the button or paddle, press the button or paddle once. The LED on the paddle will blink once blue or red,
and then revert to blinking red. To bind or unbind a button or paddle from the load press and hold that button or paddle on the
LMSW-605 or LMDM-601. The LED will switch to the other color and stay lit for one second and then resume blinking red. Each time
you press and hold the paddle or button, it will cycle to the next option:
• Blue – The button or paddle is bound to the load.
• Red – The button or paddle is not bound to the load.
Step 3 Exit Push n' Learn
Press and hold the Config button until the red LED turns OFF, approximately 3 seconds.
When you reset the LMRC-611MCC, the Channel and Network ID will return to their default values. Note that
if switches and sensors were previously paired to the room controller, they will still remain set to the previous
Channel and Network ID, but will not be in communication with the room controller and so will not control the load.
However, in a room with multiple room controllers, the other room controllers would still be paired to the switches
and sensors and those loads would respond.
There are two ways to reset the LMRC-611MCC:
• Press the Config button 10 times. The LED will blink green each time the Config button is pressed (except for
the 7th press which will blink blue). On the 10th press, the LED will blink red. Then it will turn red again and
then briefly turn white indicating it is rebooting.
• On the front of the room controller, is a small hole that will fit a paper clip. Use a paper clip to depress the button inside that hole
and hold for 15 seconds. When you first press the reset button, the LED will blink red once, then after the 15 seconds will reboot
and the LED will briefly turn white, indicating it is rebooting.
NOTE: You can also reset the LMDL-600 from the DLM Config App.
If you want to re-pair a room controller that has been reset, the easiest way is to use the DLM Config app, setting the room
controller back to the previously used Network ID.
and Android
devices. Search "DLM Config" on your device to download.
®
®
PLUG N' GO
UNIT ADJUSTMENT – PUSH N' LEARN (PNL)
RESETTING THE LMRC-611MCC
Config button &
red LED
5
Blue LED
Blue LED ON when load
is ON.
Load button:
Press & release for ON/
OFF.
Press & hold to Dim.
Reset button
loading