Close limit
Figure 15: First adjust points A, B, C so that they are on the same line. Make
sure the boom is perpendicular to the ground.
Figure 16: Adjust the small outer metal sheet with a cross screwdriver to block
the right photoelectric switch.
Then tighten the compression nut.
Fig.19
A
C
B
Functions parameters
Fucntions definition
F0
Factory setting (caution!)
F1
Micro-adjustment of the open limit (for optional digital decoder)
F2
Micro-adjustment of the close limit (for optional digital decoder)
F3
Auto close timer. Maximum 99 seconds
Default: 00 (auto close function is disabled)
F4
00: normal mode (default)
01: counting mode
F5
00: normal mode (default)
01: the barrier stays open
F6
01: LEDs stay on when the barrier is opened to limit (default)
00: LEDs go out (optional on this model)
F7
01: encoder value (default)
00: operation status
Fig.20
compression nut
15
interior small sheet
exterior small sheet