Installation Place
• A place which provides a specified space around
the outdoor unit.
• A place where the operation noise and discharged
air are not given to your neighbors.
• A place that is not exposed to a strong wind.
• A place that does not block a passage.
• When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
• There must be sufficient space for carrying in the
unit.
• A place where the drain water does not make any
problem.
CAUTION
1. Install the outdoor unit at a place where dis-
charge air is not blocked.
2. When an outdoor unit is installed in a place that
is always exposed to a strong wind like a coast
or on a high storey of a building, secure a
normal fan operation by using a duct or a wind
shield.
3. When installing the outdoor unit in a place that
is constantly exposed to a strong wind such as
the upper stairs or rooftop of a building, apply
the windproof measures referring to the follow-
ing examples.
1) Install the unit so that its
discharge port faces to
the wall of the building.
Keep a distance 500 mm
or more between the unit
and the wall surface.
2) Supposing the wind direction during the
operation season of the air conditioner, install
the unit so that the discharge port is set at
right angle to the wind direction.
Strong
wind
4. Installation in the following places may result in
some troubles. Do not install the unit in such
places below.
• A place full of machine oil.
• A place full of sulphuric gas.
• A place where high-frequency radio waves
are likely to be generated as from audio
quipment, welders, and medical equipment.
Strong
wind
4
Necessary Space for Installation
Obstacle at rear side
<Upper side is free>
1. Single unit installation
2. Obstacles at both right and left sides.
150
or more
3. Serial installation of two or more units
150
300
or more
or more
The height of the obstacle should be lower
than the height of the outdoor unit.
<Obstacle also at the upper side>
or more
Obstacle at front side
<Upper side is free>
1. Single unitIn installation
2. Serial installation of two or more units
The height of the
obstacle should be
lower than the height
of the outdoor unit.
300
or more
300
300
or more
or more
150